2.3
Changing parameters
Depending on the set system code number and the activated functions, not all parameters listed
in the parameter list in the Appendix (–> section 12.2) might be available.
The parameters are grouped by topics:
4
PA1: Rk1 (Heating circuit 1)
4
PA2: Rk2 (Heating circuit 2)
4
PA3: Not applicable
4
PA4: DHW heating
4
PA5: System-wide parameters
4
PA6: Communication parameters
1.
Turn the rotary switch to
Display: 0 0 0 0
2.
Set valid key number [q].
3.
Confirm key number [ ].
Display: PA_
4.
Select parameter level [q].
5.
Open parameter level [ ].
6.
Select parameter [q].
7.
Activate editing mode for the parameter [ ].
blinks.
8.
Edit the parameter [q].
9.
Confirm the parameter [ ].
To adjust additional parameters in the open parameter level, repeat steps 6 to 9.
10. Select End [q].
11. Exit parameter level [ ].
To adjust additional parameters in another parameter level, repeat steps 4 to 9.
12. Return the rotary switch to normal switch position
(configuration and parameter level).
(information level).