Reset To Default Settings - Samson TROVIS 5578-E Translation Of Original Instructions

Heating and district heating controller
Table of Contents

Advertisement

Switch position
Parameters
HC1 OT deactivation value
HC2 OT deactivation value
HC3 OT deactivation value
HC11 OT deactivation value
HC12 OT deactivation value
HC13 OT deactivation value

5.4 Reset to default settings

All parameters set over the rotary switch as well as parameters in the PA1, PA2, PA3, PA11,
PA12 and PA13 parameter levels can be reset to their default settings (WE). This does not
apply to the maximum flow temperature and the return flow temperature limits in PA1 and
PA2.
KA 5578-E EN
WE
Value range
15.0 °C
–50.0 to 50.0 °C
15.0 °C
–50.0 to 50.0 °C
15.0 °C
–50.0 to 50.0 °C
15.0 °C
–50.0 to 50.0 °C
15.0 °C
–50.0 to 50.0 °C
15.0 °C
–50.0 to 50.0 °C
Turn the rotary switch to
point). The day and night set points appear on the display
one after the other.
Î Only those day and night set points are available for se-
lection which can be controlled by the selected system.
Note
The deactivation values are located in a separate menu (de-
activation values) for systems with three control circuits.
q Select the set point.
¼ Activate editing mode for set point.
q Adjust the set point.
¼ Confirm setting.
Proceed in the same manner to adjust further set points.
After adjusting all the set points:
Turn the rotary switch back to
(day set point) or
(operating level).
Operation
(night set
21