System-wide functions
represents the time which elapses until the integral component has changed the output signal to
the same extent as the immediate change performed by the proportional component (the
greater T
, the slower the rate of change). Due to the derivative component, any change of the
N
system deviation is incorporated into the output signal with a certain gain (the greater T
stronger the change).
Function
Control mode
7.9

Releasing a control circuit/controller over the binary input

The release of an individual control circuit or the controller using the binary input only becomes
effective when the respective control circuit is in automatic mode (icon
circuit always works in automatic mode; the deactivated control circuit behaves as if it were
transferred to stand-by mode .
It remains active, however, in any case for processing of external demand. The control circuit
can be released via the binary input when the binary input is either a make contact (bE = 0) or a
break contact (bE = 1).
Note:
In systems with supplementary heating circuit without a valve (Anl 2.x, 4.x), BE1 only influences
the operation of this heating circuit.
In system Anl 3.0, BE1 influences the operation of the entire controller (except for processing of
an external demand).
Functions
Release Rk1 at BE1
Release Rk2 at BE2
Release controller at BE1
74
EB 5573 EN
WE
Configuration
1
CO1 -> F12 - 1
2.0
KP (proportional gain) / 0.1 to 50.0
120 s
Tn (reset time) / 1 to 999 s
0 s
TV (derivative-action time) / 0 to 999 s
45 s
TY (valve transit time) / 5, 10, 15, ..., 240 s
WE
0
bE=1
0
bE=1
0
1
). The released control
Configuration
CO1 -> F14 - 1
bE=1, bE=0
CO2 -> F14 - 1
bE=1, bE=0
CO5 -> F15 - 1
bE=1, bE=0