Dhw Heating In Instantaneous Heating System - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Functions of the DHW circuit
Parameters
Hysteresis**
Charging temperature boost***
Max. charging temperature
Lag of storage tank charging pump
*
Parameters serve as limitation of the adjustment range for the DHW temperature to be set
at the rotary switch
** Deactivation value T = DHW temperature + hysteresis
*** Charging temperature T = DHW temperature + charging temperature boost
6.3

DHW heating in instantaneous heating system

Fig. 11 · Schematics of an instantaneous heating system
The control of the required DHW temperature at the flow sensor VF is only active during
times-of-use of the circulation pump ZP.
Parameters
DHW temperature set point
Sustained DHW temperature
Parameters
Min. DHW temperature
Max. DHW temperature
64
EB 5573 EN
VF
ZP
WE
55.0 °C
40.0 °C
WE
40.0 °C
60.0 °C
WE
Parameter level / Range of values
5.0 °C
PA4 / 0.0 to 30.0 °C
10.0 °C
PA4 / 0.0 to 50.0 °C
80.0 °C
PA4 / 20.0 to 130.0 °C (only with VF4)
1.0
PA4 / 0.0 to 10.0
WW
VF
ZP
WW
KW
KW
Switch position / Range of values
/ Min. to max. DHW temperature
/ Min. to max. DHW temperature
Parameter level / Range of values
PA4 / 5.0 to 90.0 °C
PA4 / 5.0 to 90.0 °C
Flow sensor
Circulation pump
Hot water
Cold water