Ini Level (Resetting The Process Control Station To Its Default Values) - Samson Trovis 6400 Mounting And Operating Instructions

Automation system, process control stations
Table of Contents

Advertisement

Operation

6.12. Ini level (resetting the process control station to its default values)

Resetting the process control station to its default values can be useful in the start-up phase or
when the control tasks to be solved with the process control station have changed. This function
is based on the setting of configuration block C56. The Ini level can only be accessed when
C56 > 1.
C56
-1
-2
-3
-4
-5
-6
-7
-8
-9
The following steps have to be carried out:
The process control station is in the OPERATING level.
1.
Set configuration block C56>1 (see above and section 6.4., p.36), then exit the CONFI-
GURATION level again.
2.
Press A key. I-O appears on the display.
3.
Press D key. Ini appears on the display.
4.
Press A key twice. End and Ini appear on the display.
5.
Press F key to exit this level.
Note:
After having executed this function, configuration block C56 is only reset to C56-1 when it was
previously set to C56-2 or C56-3! With all other settings, the Ini level remains active! We
therefore recommend to reset the configuration block to C56-1 after carrying out the function,
in order to prevent the control station from starting up by mistake.
Resetting to default values
No
Configuration and parameterization
Configuration
Parameterization
Zero and span adjustment of the analog inputs
Span adjustment of the analog outputs
Code number
Controller ID number
Adaptation parameters
Ini level (resetting the process control station to its default values)
45