Wiring field-supplied actuators to the analog output

You can wire a high-torque actuator or parallel actuators to the controller's 0–10 Vdc analog output.

High-torque actuators

You can wire one of the following Belimo actuators to the VVT Zone Controller's analog output instead of using
the controller's built-in, 35 in.-lb actuator.
NMX24-MFT P-10028
AMX24-MFT P-10028
Install the actuator according to the manufacturer's instructions.
1
Wire the actuator to the controller using the diagram below.
2
NOTE For proper operation and to prevent damage to the devices, use the same polarity for the actuator's
power and the VVT Zone Controller's power.
VVT Zone Controller
90 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
180 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
27