Alarms; Linkage - Carrier VVT Zone Installation And Startup Manual

Hide thumbs Also See for VVT Zone:
Table of Contents

Advertisement

Alarms

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Space Temperature – Indicates if the space temperature exceeds the high or low alarm limit. R:
Alarming Temperature – Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the Space Temperature alarm (above)
is in Alarm.
Alarm Limit Exceeded – Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the Space
Temperature alarm (above) is in Alarm.
Space Temp Sensor – Indicates if the space temperature sensor fails.
Indoor Air Quality – Indicates if the occupied CO
Alarm Limit.
Supply Air Temperature – Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
Filter – Indicates if the filter's runtime hours exceeds the runtime alarm limit.
Space Relative Humidity – Indicates if the relative humidity exceeds the high RH alarm limit.
Network OAT - Indicates if the controller is not receiving a valid OAT value over the network.
Airside Linkage Status – If the controller is the VVT Master, Alarm indicates that it lost
Linkage communications with the air source. If the controller is a slave, Alarm indicates that
it lost Linkage communications with the VVT master.

Linkage

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Airside Linkage
Click Linkage Collector/Linkage Provider to access the microblock popup's Summary
and Details tabs. See the microblock popup's Help files for more detailed
explanations.
Linkage Collector – Set the Number of Providers to the total number of controllers in
the linked system, including the bypass and VVT Master.
VVT Zone Controller
Properties
Equipment
>
HOME
ALARM
>
level exceeds the Occupied High CO2
2
Properties
Equipment
>
>
HOME
CONFIG
LINKAGE
>
>
Alarms
>
Range
R:
R:
R:
R:
R:
R:
R:
R:
R:
Linkage
Default/Range
D:
1
R:
1 to 32
Normal/Alarm
-56 to 245°F
-56 to 245°F
Normal/Alarm
Normal/Alarm
Normal/Alarm
Clean/Dirty
Normal/Alarm
Normal/Alarm
Normal/Alarm
65