Installation

Linked actuators

You can wire up to 4 of the following Belimo actuators to the VVT Zone Controller's analog output. Use like
actuators so that travel times and other parameters coincide.
LMX24-MFT P-10028
NMX24-MFT P-10028
AMX24-MFT P-10028
Install the actuators according to the manufacturer's instructions.
1
Wire the actuators to the controller using the diagram below.
2
Set the direction rotation switch on each actuator to CW.
3
IMPORTANT! If slaving 45° actuators, you must go to Properties > I/O Points > Hot Water Valve Max and
change scaling to 200 for the slave actuator to correctly track the primary actuator.
NOTE Maintain polarity if using the same power supply for more than one actuator.
28
45 in.-lb actuator with 0–10 Vdc control
90 in.-lb actuator with 0–10 Vdc control
180 in.-lb actuator with 0–10 Vdc control
VVT Zone Controller

Hide quick links: