For each zone in the system that was balanced, go to its Pressure Dependent Control > Details tab, then
4
click Automatic Control to return the zone to normal control.
In the tree, select the air source controller, then do one of the following.
5
a)
For an RTU Open or WSHP Open controller, go to Properties > Equipment > Configuration > Service
Configuration > Service Test and disable Service Test and Fan Test
b)
For any equipment whose wiring was disconnected to insure that only the fan only was running,
reconnect it the wires for normal operation.
CAUTION You must complete steps 4 and 5 to prevent loss of temperature control to the space and to
maintain normal operation of the system.
VVT Zone Controller
.
39