Start-up

Unit Configuration properties

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Heat Enable
– Enables the reheat function.
Parallel Fan Heat On Delay – The delay in reheat coming on after the zone has a
heating demand. If the Term Type is Parallel, this allows the fan time to use plenum air
to heat the space prior to bringing mechanical reheat. If the Term Type is Single Duct
we recommend that you set this value to 1 minute.
DCV Max Vent Damper Pos
override the damper to. When active, the damper modulates to the temperature
control position or the IAQ override position, whichever is greater.
Heating Lockout Temperature
temperature exceeds this value. Supplemental reheat is enabled when the outside air
temperature falls below a fixed hysteresis of 2°F. This function is active only if there is
a valid network outside air temperature.

Setpoint properties

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Heating Capacity
– Used for Optimal Start, this is the rate at which the zone
temperature changes when the heating system runs at full capacity to maintain
designed occupied heating setpoint.
Heating Design Temp
– The geographically-based outdoor air temperature at which the
heating system must run constantly to maintain comfort. This information is available
in ASHRAE publications and most design references.
Cooling Capacity
– Used for Optimal Start, this is the rate at which the zone
temperature changes when cooling system runs at full capacity to maintain designed
occupied cooling setpoint.
Cooling Design Temp
– The geographically-based outdoor air temperature at which the
cooling system must run constantly to maintain comfort. This information is available in
ASHRAE publications and most design references.
30
Properties
>
HOME
CONFIG
>
– The maximum damper position that the IAQ function can
– Supplemental reheat is disabled if outside air
Properties
Equipment
>
HOME
CONFIG
>
Equipment
Configuration
>
UNIT
>
Configuration
>
SETPOINT
>
Unit Configuration
>
Default/Range
D:
Enable
R:
Disable/Enable
D:
15 minutes
R:
0 to 30 minutes
,
D:
70%
R:
0 to 100%
D:
70°F
R:
-60 to 150°F
Setpoint Configuration
>
Default/Range
D:
5°F/hr
R:
0 to 120°F/hr
D:
0°F
R:
-100 to 150°F
D:
5°F/hr
R:
0 to 140°F/hr
D:
100°F
R:
-100 to 150°F
VVT Zone Controller