Performing System Checkout - Carrier VVT Zone Installation And Startup Manual

Hide thumbs Also See for VVT Zone:
Table of Contents

Advertisement

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Linkage Collector – Set the Number of Providers
in the linked system, including the bypass and VVT Master.
Linkage Provider – Enter the MS/TP Network Number and MAC Address of the
linked air source controller.
Network Number
Address
Linkage Zone Type
– Select whether the controller is a Master or a slave.
Select
VAV Master
if the controller is the Master or a sub-master in a VAV
application.
Select
VVT Master
only if the controller is the Master in a VVT application. VVT
applications do not support sub-masters.
Linkage Callers
– The minimum number of zones required to make the air source go
into heating or cooling mode. 1 is typical for systems with 8 zones or less. For larger
systems, increase the number by 1 for each 6 zones. For example, 3 linkage callers
for a 20 zone system.

Performing system checkout

Verify that all power and communication connections are correct and tight.
1
Verify that all zone terminals, ductwork, and zone controllers are properly installed and set according to
2
installation instructions and job requirements.
Verify that all air duct connections are tight.
3
Verify that zone terminal fans and system controls operate properly. Verify that actuator screws are
4
properly tightened.
At the zone terminals, check electrical system and connections of any optional electric reheat coil. If hot
5
water reheat is used, check piping and valves against job drawings.
Verify that all zone terminal dampers are fully open.
6
If using an air source with field-installed controls, make sure controls and sensors have been installed
7
and wired per manufacturer installation instructions.
Verify that the air source motor starter and, if applicable, the Hand/Off/Auto (HOA) switch are installed
8
and wired.
Verify that the area around the air source is clear of construction dirt and debris.
9
10 Verify that final filters are installed in the air handler(s). Dust and debris can adversely affect system
operation.
11 Verify that the space sensor and all optional sensors are reading correctly.
VVT Zone Controller
Properties
Equipment
>
>
HOME
CONFIG
LINKAGE
>
>
to the total number of controllers
Linkage
Default/Range
D:
1
R:
1 to 32
D:
0
R:
0 to 65535
D:
0
R:
0 to 127
D:
Slave
R:
Slave
VVT Master
VAV Master
D:
1
R:
1 to 64
35