6.5.5

Supplementary Power Supply Regulations

The WAGO-I/O-SYSTEM 750 XTR can also be used in shipbuilding applications
and onshore/offshore installations (e.g., platforms, loading facilities), as well as in
telecontrol applications. This is possible via certification under the standards of
leading agencies such as Germanischer Lloyd and Lloyds Register.
For standard-compliant application in substation instrumentation and control,
telecontrol systems, railway technology or shipbuilding certified operation, field-
side power supply filter 750-624/040-001 or power supply filter 750-626/040-000
are generally to be used for XTR module groups.

Table 17: Filter Modules for 24 V Power Supply

Item No.
750-626/040-000
750-624/040-001
Therefore, the following power supply requirements must be observed:

Figure 21: Power Supply Concept

The 24 V system power supply for the fieldbus coupler/controller must be filtered
and protected against overvoltage. Therefore, the power must be supplied via
power supply filter 750-626/040-000.
Manual
Version 1.2.0
Description
Description
Power supply
System and field supply with filtering (24 V,
filter
0 V), i.e., fieldbus coupler/controller and bus
power supply (750-613/040-000)
Field-side
24 V field supply with filtering
power supply
filter
Connect Devices