18
System Description
3.5.3

Connection Type

Table 5: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Table 6: Technical Data – Power Jumper Contacts
Power jumper contacts
Voltage drop at I
Current over power jumper contacts
Table 7: Technical Data – Internal Bus
Data contacts
3.5.4

Climatic Environmental Conditions

Table 8: Technical Data – Climatic Environmental Conditions
Operating temperature range
Storage temperature range
Relative humidity
Elevation above sea level
without temperature derating
with temperature derating
max.
Stress due to contaminants
Max. contaminant concentration at a
relative humidity < 75%
Special conditions
1)
Short-term condensation acc. class 3K7 / IEC EN 60721-3-3 (except wind-driven precipitation,
water and ice formation) permitted
Pos : 20.3 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
max.
max.
1)
WAGO-I/O-SYSTEM 750 XTR
750-xxxx/0040-xxxx Design Notes /XTR
®
CAGE CLAMP
Push-in CAGE CLAMP
0.25 mm² ... 2.5 mm², AWG 24 ... 14 /
0.25 mm² ... 1.5 mm², AWG 24 ... 16
8 mm ... 9 mm / 0.33 in
Blade/spring contact, self-cleaning
< 1 V/64 modules
10 A
Slide contact, hard gold plated,
self-cleaning
−40 °C ... +70 °C
−40 °C ... +85 °C
95 %
0 m ... 2000 m
2000 m ... 5000 m: 0.5 K per 100 m
5000 m
Acc. IEC 60068-2-42 and IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
The components may not be used without
additional measures at locations in which
dust, corrosive fumes, gases or ionized
radiation can occur.
/
®