Modbus
Data type /
register
Size in bytes
6244
Unsigned / 4
7032
Unsigned / 4
6247
Unsigned / 2
6249
Unsigned / 2
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
Parameter
Description
Alarm items 8
Bitwise enabling of
alarms in alarm items 8.
Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 145).
Alarm items 9
Bitwise enabling of
alarms in alarm items
9.Set bit means alarm
item simulation activa‐
ted. See Alarm items
(Page 145).
Alarm class
Bit encoded selection
of alarm classes.
Applicable if simulation
mode = 2. Set bit
means alarm class sim‐
ulation activated:
Bit 0: Process value
alarm (PA)
Bit 1: Process value
warning (PW)
Bit 2: Maintenance
alarm (MA)
Bit 3: Maintenance
warning (MW)
Bit 4: Maintenance re‐
quired (MR)
Bit 5: Function check
(FC)
NAMUR status
Bit encoded selection
of NAMUR status sig‐
nals. Applicable if simu‐
lation mode = 2. Set bit
means NAMUR status
signal simulation acti‐
vated:
Bit 0: Out of specifica‐
tion (PA, PW)
Bit 1: Failure (MW)
Bit 2: Maintenance re‐
quired (MR, MD)
Bit 3: Function check
(FC)
4.10 Modbus holding registers tables
Default value
Value range /
[unit]
Setting options
(unit register)
0
-
0
-
0
0 - 63
0
0 - 15
MODBUS commands
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
185