Siemens SITRANS F Coriolis FCT030 Function Manual page 121

Flowmeters modbus from firmware 4.0
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10624
Unsigned / 2
10629
Float / 4
10635
Float / 4
10641
Float / 4
10620
Float / 4
10608
Float / 4
10610
Float / 4
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
Parameter
Description
Fail-safe behav‐
Reaction in case of a
ior
fault at the current in‐
put.
Fail-safe value
Input value in case of a
pressure
fault and when Fail-
safe behavior config‐
ured to 1. Applicable if
process value (10623)
= 0.
Fail-safe value
Input value in case of a
temperature
fault and when Fail-
safe behavior config‐
ured to 1. Applicable if
process value (10623)
= 1.
Fail-safe value
Input value in case of a
density
fault and when Fail-
safe behavior config‐
ured to 1. Applicable if
process value (10623)
= 2.
Trimmed input
Provides the measured
value
current value.
Offset adjust‐
Command to trim the
ment
lower range value of
the analog input.
Provide a loop current
of 4.0 mA, read out the
value of Trimmed input
value and write the val‐
ue to this register.
Gain adjustment Command to trim the
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an am‐
pere meter and write
the measured value to
this register.
4.10 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
0
● 0: Last valid value
● 1: Custom value
0.0
-
[Pa]
(7548)
Min. medium
-
temperature
[°C]
(7700)
600.0
-
[kg/m3]
(7600)
-
-
-
-
-
-
MODBUS commands
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read
only
Write on‐
ly
Write on‐
ly
121