Siemens SITRANS F Coriolis FCT030 Function Manual page 107

Flowmeters modbus from firmware 4.0
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10524
Unsigned / 2
10535
Float / 4
10541
Float / 4
10520
Float / 4
10508
Float / 4
10510
Float / 4
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
Parameter
Description
Fail-safe behav‐
Reaction in case of a
ior
fault at the current in‐
put.
Fail-safe tem‐
Input value in case of a
perature value
fault and when Fail-
safe behavior (10524)
configured to 1. Appli‐
cable if Process value
(10523) = 1.
Fail-safe value
Input value in case of a
density
fault and when Fail-
safe behavior (10524)
configured to 1. Appli‐
cable if Process value
(10523) = 2.
Trimmed input
Provides the measured
value
current value.
Offset adjust‐
Command to trim the
ment
lower range value of
the analog input.
Provide a loop current
of 4.0 mA, read out the
value of Trimmed input
value and write the val‐
ue to this register.
Gain adjustment Command to trim the
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an am‐
pere meter and write
the measured value to
this register.
4.10 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units register)
0
● 0: Last valid value
● 1: Custom value
Min. medium
-
temperature
[°C]
(7700)
600.0
-
[kg/m
]
3
(7600)
-
-
-
-
-
-
MODBUS commands
Access
level
Read /
write
Read /
write
Read /
write
Read
only
Write on‐
ly
Write on‐
ly
107