Siemens SITRANS F Coriolis FCT030 Function Manual page 112

Flowmeters modbus from firmware 4.0
Table of Contents

Advertisement

MODBUS commands
4.10 Modbus holding registers tables
Modbus
Data type /
register
Size in bytes
9386
Float / 4
9388
Float / 4
Channel 4 frequency output settings
Table 4-44
Channel 4 frequency output settings
Modbus
Data type /
register
Size in bytes
9404
Unsigned / 2
9410
Unsigned / 2
9435
Float / 4
9437
Float / 4
112
Parameter
Description
Offset adjust‐
Command to trim the
ment
lower range value of
the loop current.
Simulate a loop current
of 4.0 mA, measure the
current with an ampere
meter and write the
measured value to this
register.
Gain adjustment Command to trim the
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an am‐
pere meter and write
the measured value to
this register.
Parameter
Description
Process value
Select process value
for the current output.
Flow direction
Flow direction filter ap‐
plicable for Process val‐
ues (9404) set to 0, 1,
19, or 27.
Frequency val‐
Upper frequency value.
ue high
Upper nominal output
range boundary.
Frequency val‐
Lower frequency value.
ue low
Lower nominal output
range boundary.
Default value
Value range /
[units]
Setting options
(units register)
-
0 - 25
-
0 - 25
Default value
Value range /
[units]
Setting options
(units register)
0
● 0: Mass flow
● 1: Volume flow
● 2: Density
● 3: Medium
temperature
0
● 0: Positive direction
● 1: Negative direction
● 2: Positive and
negative directions
● 3: Positive and
negative directions
(symmetric mode)
10000.0
0.0 - 12500.0
[Hz]
0.0 Hz
0.0 - 12500.0
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
Access
level
Write on‐
ly
Write on‐
ly
Access
level
Read /
write
Read /
write
Read /
write
Read /
write