Siemens SITRANS F Coriolis FCT030 Function Manual
Siemens SITRANS F Coriolis FCT030 Function Manual

Siemens SITRANS F Coriolis FCT030 Function Manual

Flowmeters modbus from firmware 4.0
Table of Contents

Advertisement

Quick Links

SITRANS F
Coriolis Flowmeters
FCT030 Modbus (From firmware
4.0)
Function Manual
06/2018
A5E39931813-AB
Introduction
Communication
Commissioning
MODBUS commands
Definitions
1
2
3
4
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS F Coriolis FCT030

  • Page 1 Introduction Communication Commissioning SITRANS F MODBUS commands Coriolis Flowmeters FCT030 Modbus (From firmware Definitions 4.0) Function Manual 06/2018 A5E39931813-AB...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Introduction..............................7 Purpose of this documentation....................7 Document history........................7 Product compatibility........................8 Communication.............................9 System integration........................9 System configuration........................9 System wiring.........................12 Connecting..........................14 2.4.1 Connecting the Modbus (CH1)....................14 Commissioning............................17 General requirements......................17 Operating via SIMATIC PDM....................17 Functions in SIMATIC PDM....................17 Commissioning steps......................17 Initial Setup..........................17 Adding a device to communication network................20 Configuring a new device.......................21 Wizard - Quick Start via PDM....................22...
  • Page 4 Table of contents Access control........................40 4.10 Modbus holding registers tables....................41 4.10.1 Modbus holding registers tables (intro)..................41 4.10.2 Process values........................42 4.10.3 Totalizers..........................44 4.10.4 Units............................46 4.10.5 Setup............................58 4.10.5.1 Sensor settings........................58 4.10.5.2 Density...........................59 4.10.5.3 Aerated flow...........................61 4.10.5.4 Zero point adjustment......................62 4.10.5.5 Quality codes for process values...................64 4.10.5.6 Process values........................69 4.10.5.7...
  • Page 5 Table of contents Definitions..............................191 Definitions..........................191 Index.................................195 FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 6 Table of contents FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 7: Introduction

    Mass 2100 FC300 FCS400 and FSC300 In order to operate a Coriolis flow meter, you also need Operating Instructions. See Flow documentation (http://www.siemens.com/flowdocumentation) Document history The following table shows major changes in the documentation compared to the previous edition. The most important changes in the documentation when compared with the respective previous edition are given in the following table.
  • Page 8: Product Compatibility

    Introduction 1.3 Product compatibility Product compatibility Edition Remarks Product compatibility Compatibility of device integration package 06/2017 First revision HW revision 03 Service channel: SIMATIC 5.00.xx-xx V8.2 Service Pack 1 or later Compact FW revision 4.xx.xx-xx Modbus: SIMATIC V8.2 Serv‐ 5.00.xx-xx Remote FW revision 4.xx.xx-xx ice Pack 1 or later HART: SIMATIC V8.2 Serv‐...
  • Page 9: Communication

    Modbus RTU network in non-hazardous or hazardous areas. Many details of network design are beyond the scope of these operating instructions. The points below provide an overview of the major design criteria. For further details contact Siemens. System configuration Non-hazardous areas The following figures show examples of installations in point-to-point and multidrop configurations in non-hazardous areas.
  • Page 10 Communication 2.2 System configuration Figure 2-2 Multidrop configuration (branch) in non-hazardous area FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 11 Communication 2.2 System configuration Figure 2-3 Multidrop configuration (Daisy chain) in non-hazardous area Hazardous areas The following figures show examples of installations in point-to-point and multidrop configurations in hazardous areas. Figure 2-4 Point-to-point configuration in hazardous area FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 12: System Wiring

    Communication 2.3 System wiring Figure 2-5 Multidrop configuration in hazardous area NOTICE Flameproof conduit seals Two flameproof conduit seals are required for each device in hazardous area installations. NOTICE Equipment approved for hazardous areas Ensure that the equipment is approved for installation in hazardous areas. System wiring The device is slave in a 2-wire Modbus RTU RS 485 bus system.
  • Page 13 Communication 2.3 System wiring Topology The device supports a two-wire electrical interface in accordance with EIA/TIA-485 standard. An RS485 Modbus configuration without repeater has one trunk cable, along which devices are connected, directly (daisy chaining) or by short branch cables. Note Multidrop examples in this document show a trunk cable with short branch cables.
  • Page 14: Connecting

    Communication 2.4 Connecting Figure 2-6 Maximum cable lengths in multidrop configuration Connecting Note End Of Line (EOL) termination The FCT030 EOL termination DIP switch is default set to EOL active. To change termination setting see Setting the EOL termination DIP switches changed. 2.4.1 Connecting the Modbus (CH1) 1.
  • Page 15 Communication 2.4 Connecting 5. Connect wires to terminals using wiring tool, field mount transmitter Modbus ④ In + (B) ⑤ In - (A) ⑥ Out + (B) ⑦ Out - (A) Functional Earth 6. Connect wires to terminals using wiring tool, wall mount transmitter. Modbus ④...
  • Page 16 Communication 2.4 Connecting FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 17: Commissioning

    Commissioning General requirements Before commissioning it must be checked that: ● The device has been installed and connected in accordance with the guidelines provided in the Operating Instruction for FCT030 transmitter Operating via SIMATIC PDM SIMATIC PDM is a software package used to commission and maintain process devices. Functions in SIMATIC PDM SIMATIC PDM monitors the process values, alarms and status signals of the device.
  • Page 18 Deactivating buffers for RS 485 COM port This deactivation is required to align SIMATIC PDM for Windows® operating systems. Note Support for Windows operating systems can be found here: support.automation.siemens.com (http://support.automation.siemens.com) 1. Click Start → Control Panel to begin configuration.
  • Page 19 You can locate the EDD in the SIMATIC PDM Device Library under Devices → Modbus → Sensors → Flow → Coriolis → Siemens AG → SITRANS FC430 and FC330. Check the product page of our website (www.siemens.com/FC430) under Support > Software downloads, to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF).
  • Page 20: Adding A Device To Communication Network

    – Right-click Modbus Network and select Insert New Object → Object. – Click on Assign Device Type, and select Devices → Modbus → Sensors → Flow → Coriolis → SIEMENS AG → SITRANS FC Click OK two times. Figure 3-2 Assigning Modbus device to network 2.
  • Page 21: Configuring A New Device

    Commissioning 3.7 Configuring a new device – Select the Communication tab and configure the communication parameters. The transmitters default settings are: - Transmission rate: 19200 baud - Parity: even Figure 3-3 Modbus net object properties – Click OK. 3. Set up the COM interface: –...
  • Page 22: Wizard - Quick Start Via Pdm

    Commissioning 3.8 Wizard - Quick Start via PDM 1. Check that you have the most recent EDD, and if necessary update it, see Updating the Electronic Device Description (EDD) in Initial Setup (Page 17). 2. Launch SIMATIC Manager. 3. Right-click on SITRANS FC and select Open Object to open SIMATIC PDM. 4.
  • Page 23 Commissioning 3.8 Wizard - Quick Start via PDM Step 1 - Identification Note The layout of the dialog boxes shown may vary according to the resolution setting for your computer monitor. The recommended resolution is 1280 x 960. FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 24 Commissioning 3.8 Wizard - Quick Start via PDM 1. Click on Read Data from Device to upload Quick Start parameter settings from the device to the PC/PG and ensure PDM is synchronized with the device. 2. Click on Next to accept the default values. (Descriptor, Message, and Date fields can be left blank.) Figure 3-5 Quick start step 1...
  • Page 25 Commissioning 3.8 Wizard - Quick Start via PDM Step 2 - Sensor orientation Step 2 shows an overview of the various recommended installation orientations depending on the application. Figure 3-6 Quick start step 2 FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 26 Commissioning 3.8 Wizard - Quick Start via PDM Step 3 - Sensor connection The transmitter can be ordered with M12 connection or with terminated cable (for example conduit connections). Figure 3-7 Quick start step 3 FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 27 Commissioning 3.8 Wizard - Quick Start via PDM Step 4 - Measurement conditions Configure the measurement conditions for the selected process variables. Change Flow Direction if necessary. Figure 3-8 Quick start step 4 Reduce the sensitivity of the flow measurement signal by clicking on the Pulsating Flow button and selecting the appropriate filter.
  • Page 28 Commissioning 3.8 Wizard - Quick Start via PDM Figure 3-9 Filter setting selection Step 5 - Summary Check parameter settings, and click on Back to return and revise values, Apply to save settings offline, or Apply and Transfer to save settings offline and transfer them to the device. Figure 3-10 Quick start step 5 The message Quick Start was successful will appear.
  • Page 29: Wizard - Zero Point Adjustment

    Commissioning 3.9 Wizard - Zero Point adjustment Wizard - Zero Point adjustment Open the menu Device → Wizard → Zero Point Adjustment. Select Auto. Click on Next. It is recommended to use the default settings. Change the Zero Point Adjustments Settings, if necessary.
  • Page 30: Changing Parameter Settings Using Simatic Pdm

    Commissioning 3.10 Changing parameter settings using SIMATIC PDM 3.10 Changing parameter settings using SIMATIC PDM Note Clicking on Cancel during an upload from device to SIMATIC PDM will result in some parameters NOT being updated. FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 31: Parameters Accessed Via Drop-Down Menus

    Commissioning 3.11 Parameters accessed via drop-down menus Many parameters are accessed via the online menus in SIMATIC PDM, see Parameters accessed via drop-down menus for the others. 1. Launch SIMATIC PDM, connect to the appropriate device and upload data. 2. Adjust parameter values in the parameter value field then click on Enter. The status fields read Changed.
  • Page 32 Commissioning 3.11 Parameters accessed via drop-down menus Drop-down menus Table 3-1 Device menus Device menus Description Download to Device Downloads all writable parameters to the device Upload to PC/PG Uploads all parameters from the device to the parameter table Assign address and TAG Assign communication address and TAG name Value comparison Compare values between device / project...
  • Page 33: Modbus Commands

    MODBUS commands Modbus addressing model The device allows read/write access to one holding register block. All devices are mapped to this Modbus address space. Modbus communication Table 4-1 General Modbus settings Modbus Data type / Parameter Description Default val‐ Value range / Access register Size in...
  • Page 34 MODBUS commands 4.2 Modbus communication Modbus Data type / Parameter Description Default val‐ Value range / Access register Size in Setting options level bytes [units] (units register) 8298 Unsigned / Baud rate Baud rate of Modbus interface. 19200 Bit/s ● 0: 9600 Bit/s Read / write ●...
  • Page 35: Coil Configuration

    MODBUS commands 4.3 Coil configuration Coil configuration The device provides 20 coil definitions which can be configured. Table 4-2 Coil configuration Modbus Data type / Parameter Description Default value Value range / Access lev‐ register Size in bytes [units] Setting options (units register) 10300 Unsigned / 2 Modbus coil ad‐...
  • Page 36: Modbus Register Mapping

    MODBUS commands 4.4 Modbus register mapping Modbus Data type / Parameter Description Default value Value range / Access lev‐ register Size in bytes [units] Setting options (units register) 10307 Unsigned / 4 Modbus coil bit‐ Bit mask which is compared 0 - 4294967295 Read / write mask 2 against the register value...
  • Page 37 MODBUS commands 4.4 Modbus register mapping The device provides means to remap 20 Modbus registers. Table 4-3 Modbus register mapping Modbus Data type / Parameter Description Default value Value range / Access register Size in [units] Setting op‐ level bytes (units register) tions 10448...
  • Page 38: Integer Byte Order

    MODBUS commands 4.6 Float transmission Integer byte order The device is able to adjust the byte order of integer values. Table 4-4 Integer byte order Modbus Data type / Parameter Description Default value Value range / Access register Size in [units] Setting op‐...
  • Page 39: Float Byte Order

    MODBUS commands 4.8 Modbus function codes Float byte order The device is able to adjust the byte order of floating-point values. Table 4-5 Float byte order Modbus Data type / Parameter Description Default value Value range / Access register Size in [units] Setting op‐...
  • Page 40: Access Control

    Slave ID 1 byte Sensor device type 0: SITRANS FC Run indicator 1 byte 255: Running Manufacturer name 12 bytes SIEMENS Product name 32 bytes SITRANS F Product firmware 16 bytes version 2 bytes Access control Access control manages whether the Modbus master is allowed to modify device parameters.
  • Page 41: Modbus Holding Registers Tables

    MODBUS commands 4.10 Modbus holding registers tables If the device is defined as a custody transfer (CT) device and the CT write protection DIP switch is ON (locked), the device will deny all writes to CT parameters independent of the access control.
  • Page 42: Process Values

    MODBUS commands 4.10 Modbus holding registers tables 4.10.2 Process values Table 4-8 Process values for standard FC applications Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 3000 Float / 4 Mass flow...
  • Page 43 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8969 Float / 4 Amount on CH2 Current totalized Read amount according to (Mass: 7400 / only pulse output channel 2...
  • Page 44: Totalizers

    MODBUS commands 4.10 Modbus holding registers tables 4.10.3 Totalizers Table 4-10 Totalizers Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8300 Float / 4 Totalizer 1 value Totalized value of total‐ Read / izer 1.
  • Page 45 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8416 Float / 4 Totalizer 2 pre‐ Preset value which will Read / set value be used when Totalizer...
  • Page 46: Units

    MODBUS commands 4.10 Modbus holding registers tables 4.10.4 Units Table 4-11 Units settings for values and quantities communicated via Modbus Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7500 Unsigned / 2...
  • Page 47 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) ● 171: BBL31/min (1 barrel = 31 US gallons) ● 172: BBL31/h (1 barrel = 31 US gallons 7400 Unsigned / 2...
  • Page 48 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7964 Unsigned / 2 Standard vol‐ Units for ● 121: Nm³/h (normal cubic meters Read / ume flow units standard...
  • Page 49 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7600 Unsigned / 2 Density units Units for ● 91: g/cm³ (grams per cubic) Read / density val‐...
  • Page 50 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8320 Unsigned / 2 Totalizer 1 units Units for ● 60: g (grams) Read / mass quan‐...
  • Page 51 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8420 Unsigned / 2 Totalizer 2 units Units for ● 60: g (grams) Read / mass quan‐...
  • Page 52 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8521 Unsigned / 2 Totalizer 3 units Units for ● 40: US gallons Read / volume write...
  • Page 53 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8993 Unsigned / 2 Volume units Units for ● 40: US gallons Read / volume write...
  • Page 54 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9293 Unsigned / 2 Volume units Units for ● 40: US gallons Read / volume write...
  • Page 55 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9493 Unsigned / 2 Volume units Units for ● 40: US gallons Read / volume write...
  • Page 56 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8468 Float / 4 Custom volume Conversion Read / flow units factor factor for write user specif‐...
  • Page 57 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8492 Float / 4 Custom velocity Conversion Read / units factor factor for write user specif‐...
  • Page 58: Setup

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5 Setup 4.10.5.1 Sensor settings Table 4-12 General sensor settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 2100 Unsigned / 2 Flow direction Define positive and...
  • Page 59: Density

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.2 Density Density settings Table 4-13 Density settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 2127 Float / 4 Empty Tube Define threshold value 500 [kg/m...
  • Page 60 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 2442 Float / 4 Density Correc‐ Set density compensa‐ -1.999 to Read / tion tion...
  • Page 61: Aerated Flow

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.3 Aerated flow Table 4-14 Aerated Flow HMI menu ID Parameter Description Default value Value range Access level [unit] 3.9.1 Aerated Flow Filter Set the process value filter for Auto ● Off User aerated flow.
  • Page 62: Zero Point Adjustment

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.4 Zero point adjustment In the following the automatic zero point adjustment function is described. Note Preconditions Before a zero point adjustment is initiated, the pipe must be flushed, filled and at an absolute flowrate of zero preferably also at operating pressure and temperature.
  • Page 63 MODBUS commands 4.10 Modbus holding registers tables The offset value must be within the determined Zero Point Offset Limit (Modbus address 2140). Note Exceeded zero point offset limit If the offset value is greater than the configured limit, proceed as follows: ●...
  • Page 64: Quality Codes For Process Values

    MODBUS commands 4.10 Modbus holding registers tables Manual zero point adjustment In case an automatic zero point adjustment cannot be performed, it is possible to do a manual zero point adjustment by entering the zero point offset value. 1. Select Modbus address 2132 Zero Point Adjustment and set the value to 1 = Manual Zero Point Adjustment.
  • Page 65 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7609 Unsigned / 2 Density status Quality sta‐ ● Limit status bit 4 & 5: tus code of ●...
  • Page 66 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7855 Unsigned / 2 Fraction A Per‐ Quality sta‐ ● Limit status bit 4 & 5: cent status tus code of ●...
  • Page 67 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7892 Unsigned / 2 Fraction B flow Quality sta‐ ● Limit status bit 4 & 5: Read status tus code of...
  • Page 68 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8318 Unsigned / 2 Totalizer 1 sta‐ Quality sta‐ ● Limit status bit 4 & 5: Read tus code of only...
  • Page 69: Process Values

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.6 Process values Table 4-16 Volume flow settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7510 Float / 4 Low flow cut-off Volume flow limit for Sensor size 0 - max.
  • Page 70 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7405 Float / 4 Lower warning Falling below this limit -max. mass -max.
  • Page 71 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7705 Float / 4 Lower warning Falling below this min. medium min.
  • Page 72 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7808 Float / 4 Lower alarm Falling below this 0 - 100 Read / limit limit causes an...
  • Page 73 MODBUS commands 4.10 Modbus holding registers tables Table 4-24 Fraction volume flow A settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7782 Float / 4 Upper alarm Exceeding this limit 0 - 100...
  • Page 74: Totalizers

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7927 Float / 4 Lower warning Falling below this 0 - 100 Read / limit limit causes a warn‐...
  • Page 75 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8325 Float / 4 Volume upper Exceeding this limit Max. floating Read / warning limit causes a warning when...
  • Page 76 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8339 Float / 4 Standard vol‐ Falling below this limit Min. floating Read / ume lower causes an alarm when...
  • Page 77 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8427 Float / 4 Volume lower Falling below this limit Min. floating Read / warning limit causes a warning when...
  • Page 78 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8439 Float / 4 Standard vol‐ Falling below this limit Min. floating Read / ume lower causes an alarm when...
  • Page 79 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8527 Float / 4 Volume lower Falling below this limit Min. floating Read / warning limit causes a warning when...
  • Page 80: Inputs And Outputs

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8539 Float / 4 Standard vol‐ Falling below this limit Min. floating Read / ume lower causes an alarm when...
  • Page 81 MODBUS commands 4.10 Modbus holding registers tables Channel 2 current output settings Table 4-31 Channel 2 current output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8802 Unsigned / 2 Process value...
  • Page 82 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8810 Float / 4 Upper range Upper mass flow value 0.2 • max. Read / value mass flow that is mapped to the...
  • Page 83 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8878 Float / 4 Upper range Upper standard volume 0.4 % • stna‐ Read / value standard flow value that is map‐...
  • Page 84 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10008 Float / 4 Upper range Upper dimensionless Read / value dimen‐ value that is mapped to write sionless...
  • Page 85 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10064 Float / 4 Upper range Upper rate of change Read / value ROC value that is mapped to [m/s²]...
  • Page 86 MODBUS commands 4.10 Modbus holding registers tables Channel 2 frequency output settings Table 4-32 Channel 2 frequency output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8904 Unsigned / 2 Process value...
  • Page 87 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8913 Float / 4 Lower range Lower mass flow value Read / value mass flow that is mapped to the [kg/s]...
  • Page 88 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8929 Float / 4 Lower range Lower standard volume Read / value standard flow value that is map‐...
  • Page 89 MODBUS commands 4.10 Modbus holding registers tables Channel 2 pulse output settings Table 4-33 Channel 2 pulse output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8960 Unsigned / 2 Process value...
  • Page 90 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 7421 Float / 4 Fail-safe value Output value in case of 0.0 - 12500.0 Read / a fault and when Fail-...
  • Page 91 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8844 Unsigned / 4 Alarm items 2 Bit encoded selection Read / of alarm items that im‐...
  • Page 92 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 8862 Float / 4 Off delay Time to delay the trail‐ 0.0 - 100.0 Read / ing edge of the output.
  • Page 93 MODBUS commands 4.10 Modbus holding registers tables Channel 3 current output settings Table 4-36 Channel 3 current output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9102 Unsigned / 2 Process value...
  • Page 94 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9110 Float / 4 Upper range Upper mass flow value 0.2 • max. Read / value mass flow that is mapped to the...
  • Page 95 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9178 Float / 4 Upper range Upper standard volume 0.4 % • max. Read / value standard flow value that is map‐...
  • Page 96 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9115 Float / 4 Fail-safe value Output value in case of 0.0 - 25.0 Read / a fault and when Fail-...
  • Page 97 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9210 Unsigned / 2 Flow direction Flow direction filter ap‐ ● 0: Positive direction Read / plicable for Process val‐...
  • Page 98 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9219 Float / 4 Upper range Upper process density Max. density Read / value density value that is mapped to...
  • Page 99 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10136 Float / 4 Upper range Upper current value 20.0 Read / value current that is mapped to the [mA]...
  • Page 100 MODBUS commands 4.10 Modbus holding registers tables Channel 3 pulse output settings Table 4-38 Channel 3 pulse output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9280 Unsigned / 2 Redundancy...
  • Page 101 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9591 Unsigned / 2 Fail-safe activa‐ Fail-safe activation con‐ ● 0: Bad status of Read / tion condition dition.
  • Page 102 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9199 Unsigned / 2 NAMUR status Bit encoded selection ● Bit 0: Out of Read / signals of NAMUR status sig‐...
  • Page 103 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9154 Unsigned / 4 Alarm items 7 Bit encoded selection Read / of alarm items that im‐...
  • Page 104 MODBUS commands 4.10 Modbus holding registers tables Channel 3 discrete input settings Table 4-40 Channel 3 discrete input settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9131 Unsigned / 2 Input leading...
  • Page 105 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9135 Unsigned / 2 Polarity Logical polarity of dis‐ ● 0: Active high level Read / crete input signal.
  • Page 106 MODBUS commands 4.10 Modbus holding registers tables Channel 3 analog input settings Table 4-41 Channel 3 analog input settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10522 Unsigned / 2 Current mode...
  • Page 107 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10524 Unsigned / 2 Fail-safe behav‐ Reaction in case of a ●...
  • Page 108 MODBUS commands 4.10 Modbus holding registers tables General channel 4 settings Table 4-42 General channel 4 settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9301 Unsigned / 2 Operation mode Operation mode.
  • Page 109 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9306 Unsigned / 2 Current mode Mode of current output. 0 ●...
  • Page 110 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9370 Float / 4 Upper range Upper process density Max. denisty Read / value density value that is mapped to...
  • Page 111 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10212 Float / 4 Upper range Upper current value 20.0 Read / value current that is mapped to the [mA]...
  • Page 112 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9386 Float / 4 Offset adjust‐ Command to trim the 0 - 25 Write on‐...
  • Page 113 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9415 Float / 4 Upper range Upper volume flow val‐ 0.4 % • max. Read / value volume ue that is mapped to...
  • Page 114 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9423 Float / 4 Upper range Upper medium temper‐ Max. medium Read / value tempera‐...
  • Page 115 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9592 Unsigned / 2 Fail-safe activa‐ Fail-safe activation con‐ ● 0: Bad status of Read / tion condition dition.
  • Page 116 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9463 Float / 4 Amount of mass Amount value to gener‐ Read / ate an output pulse.
  • Page 117 MODBUS commands 4.10 Modbus holding registers tables Channel 4 status output settings Table 4-46 Channel 3 status output settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9341 Unsigned / 2 Status mode...
  • Page 118 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9350 Unsigned / 4 Alarm items 5 Bit encoded selection Read / of alarm items that im‐...
  • Page 119 MODBUS commands 4.10 Modbus holding registers tables Channel 4 discrete input settings Table 4-47 Channel 4 discrete input settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 9331 Unsigned / 2 Input leading...
  • Page 120 MODBUS commands 4.10 Modbus holding registers tables Channel 4 analog input settings Table 4-48 Channel 4 analog input settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10622 Unsigned / 2 Current mode...
  • Page 121 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [units] Setting options level (units register) 10624 Unsigned / 2 Fail-safe behav‐ Reaction in case of a ●...
  • Page 122: Date And Time

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.9 Date and time Table 4-49 General settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6185 Unsigned / 2 Year Holds current year after 2016...
  • Page 123: Local Display

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6190 String / 16 Current time Current time in ISO Read 8610 format only (YYYY-MM-DD...
  • Page 124 Unsigned / 2 Status icons Type of alarm icons Order-specif‐ ● 0: Standard Read / shown in local display. write (Siemens) ● 1: NAMUR 6409 Float / 4 Filter time con‐ Damping filter time for 0.0 - 100.0 Read /...
  • Page 125 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9076 Unsigned / 2 value Selection of the fifth val‐ See Selectable values Read / ue.
  • Page 126 MODBUS commands 4.10 Modbus holding registers tables View 2 settings Table 4-52 View 2 settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9013 Unsigned / 2 Enable or disa‐...
  • Page 127 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8057 Unsigned / 2 Trend log time Scaling of the time axis. ●...
  • Page 128 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9026 Unsigned / 2 value Selection of the third See Selectable values Read / value.
  • Page 129 MODBUS commands 4.10 Modbus holding registers tables View 4 settings Table 4-54 View 4 settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9015 Unsigned / 2 Enable or disa‐...
  • Page 130 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8069 Unsigned / 2 Trend log time Scaling of the time axis. ●...
  • Page 131 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9032 Unsigned / 2 value Selection of the third See Selectable values Read / value.
  • Page 132 MODBUS commands 4.10 Modbus holding registers tables View 6 settings Table 4-56 View 6 settings Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9017 Unsigned / 2 Enable or disa‐...
  • Page 133: Selectable Values Dependent On The View Type

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8081 Unsigned / 2 Trend log time Scaling of the time axis. ●...
  • Page 134 MODBUS commands 4.10 Modbus holding registers tables Selected view type Setting options Six values ● 0: Mass flow ● 1: Volume flow ● 2: Density ● 3: Medium temperature ● 4: Standard volume Flow ● 5: Fraction Flow Media A ●...
  • Page 135: Process Value Filter Masks

    MODBUS commands 4.10 Modbus holding registers tables 4.10.5.12 Process value filter masks Process value filter masks Table 4-58 Process value filter masks Selected view type Setting options Process value filter mask 1 Bit coded mask to specify the process values that are filtered. Bit set means filtered: ●...
  • Page 136: Identification

    Size in [unit] Setting op‐ level bytes (unit register) tions 6592 String / 12 Manufacturer Device manufacturer. SIEMENS Read only 6104 String / 32 Product name Product name. SITRANS F Read only Also shown on the device nameplate. 6020 String / 16...
  • Page 137 MODBUS commands 4.10 Modbus holding registers tables Transmitter Transmitter FCT030 Table 4-61 Transmitter FCT030 Modbus Data type / Parameter Description Default value Value range / Access register Size in [unit] Setting op‐ level bytes (unit register) tions 8104 String / 32 Transmitter order Transmitter order number Read only...
  • Page 138 MODBUS commands 4.10 Modbus holding registers tables I/O cassette Table 4-64 I/O cassette Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 7260 String / 16 HW version Hardware version of Read the cassette.
  • Page 139: Diagnostic Events

    MODBUS commands 4.10 Modbus holding registers tables 4.10.7 Diagnostic events 4.10.7.1 Active events Table 4-67 Active events Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6200 Unsigned / 4 Active alarm Bitwise indication of ac‐...
  • Page 140 MODBUS commands 4.10 Modbus holding registers tables Table 4-68 Supported events Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6250 Unsigned / 4 Supported Bitwise indication of Read alarm items 1 supported alarms in...
  • Page 141 MODBUS commands 4.10 Modbus holding registers tables Table 4-69 Enable events Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6266 Unsigned / 4 Active alarm Bitwise indication of ac‐ Read / items 1 tive alarms in alarm...
  • Page 142 MODBUS commands 4.10 Modbus holding registers tables Acknowledge events Table 4-70 Acknowledge events Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6248 Unsigned / 2 Acknowledge Mode to acknowledge Read / ●...
  • Page 143: Diagnostic Log

    MODBUS commands 4.10 Modbus holding registers tables 4.10.7.2 Diagnostic log Table 4-72 Diagnostic log Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6600 Unsigned / 2 Newest entry Entry number of new‐...
  • Page 144 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6638 Unsigned / 2 Available en‐ Current number of Read tries available diagnostic log only entries.
  • Page 145: Alarm Items

    MODBUS commands 4.10 Modbus holding registers tables 4.10.7.3 Alarm items Table 4-73 Alarm items Group Alarm Restrictions Associated alarm class Alarm items 1 Sensor startup (Sensor alarm 1) Safety critical user parameters not valida‐ Safety critical factory parameters not vali‐ dated Safety critical factory parameters not vali‐...
  • Page 146 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 2 Auxiliary input failure (Sensor alarms 2) DSL Functional Safety event Unreliable flow measurement Failure on channel 5 or channel 6 Configuration error 2 DSL system monitor Alarm items 4 Mass flow above alarm limit (Process alarms 1)
  • Page 147 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 5 Reserved (Process alarms 2, totalizer alarms) Standard volume flow above alarm limit Only hydrocarbon and gas applications Standard volume flow above warning limit 133 Standard volume flow below warning limit 134 Standard volume flow below alarm limit Totalizer 1 above alarm limit...
  • Page 148 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 6 Mass flow simulated (Simulation alarms) Volume flow simulated Density simulated Medium temperature simulated 4 - 5 Reserved Standard volume flow simulated Totalizer 1 simulated Totalizer 2 simulated Totalizer 3 simulated Loop current simulated...
  • Page 149 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 7 Reserved (Inputs and outputs Reserved alarms) Reserved Channel 2 loop current in lower saturation 195 If channel configured to current output Channel 2 loop current in upper saturation 196 Channel 2 cable break Channel 2 output frequency too low If channel configured...
  • Page 150 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 8 Reserved (Process alarms 3) Reserved Reserved Reserved Sound velocity above alarm limit Sound velocity above warning limit Sound velocity below warning limit Sound velocity below alarm limit Flow velocity above alarm limit Flow velocity above warning limit Flow velocity below warning limit...
  • Page 151 MODBUS commands 4.10 Modbus holding registers tables Group Alarm Restrictions Associated alarm class Alarm items 9 Standard density above alarm limit Only hydrocarbon ap‐ (Process alarms 4) plications Standard density above warning limit Standard density below warning limit Standard density below alarm limit API gravity above alarm limit Only hydrocarbon ap‐...
  • Page 152: Diagnostics

    MODBUS commands 4.10 Modbus holding registers tables 4.10.8 Diagnostics 4.10.8.1 Device diagnostics Table 4-74 Device diagnostics Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 2756 Float / 4 Driver Current Actual sensor driver - [A]...
  • Page 153: Dosing

    MODBUS commands 4.10 Modbus holding registers tables 4.10.8.3 Dosing Table 4-76 Device diagnostics Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8550 Unsigned / 2 Dosing mode Select dosing modes 0: off, dosing disabled Read /...
  • Page 154 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8599 Unsigned / 2 Dosing cycle Command to reset the 0: do nothing Read / counter reset dosing cycle counter...
  • Page 155 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8608 Float / 4 Recipe 1 Target amount for dos‐ Read / amount mass ing mass flow write...
  • Page 156 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8627 Float / 4 Recipe 1 over‐ When the amount vol‐ Read / run volume flow ume flow has reached...
  • Page 157 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8780 Unsigned / 2 Recipe 2 unit Corrected volume flow 166: normal cubic meters Read / corrected vol‐...
  • Page 158 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8791 Unsigned / 2 Recipe 2 com‐ Compensation algo‐ 0: fixed compensation Read / pensation mode rithm, fixed or adaptive...
  • Page 159 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9679 Unsigned / 2 Recipe 3 unit Volume flow unit for 40: US gallons Read / volume flow...
  • Page 160 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9617 Float / 4 Recipe 3 fixed Fixed compensation Read / compensation volume flow value that write...
  • Page 161 MODBUS commands 4.10 Modbus holding registers tables Dosing - recipe 4 Table 4-80 Dosing – recipe 4 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9700 String / 16 Recipe 4 name Name of recipe param‐...
  • Page 162 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 7593 Unsigned / 2 Recipe 4 Dec. Specify the selected Read / point volume number of decimals for write...
  • Page 163 MODBUS commands 4.10 Modbus holding registers tables Dosing - recipe 5 Table 4-81 Device diagnostics Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9800 String / 16 Recipe 5 name Name of recipe param‐...
  • Page 164 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 7596 Unsigned / 2 Recipe 5 Dec. Specify the selected Read / point volume number of decimals for write...
  • Page 165: Inputs And Outputs

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9827 Float / 4 Recipe 5 over‐ When the amount vol‐ Read / run volume flow ume flow has reached...
  • Page 166 MODBUS commands 4.10 Modbus holding registers tables Channel 2 Table 4-83 Channel 2 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8803 Float / 4 Current output Output current value if Read value...
  • Page 167 MODBUS commands 4.10 Modbus holding registers tables Channel 3 Table 4-84 Channel 3 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9103 Float / 4 Current output Output current value if Read value...
  • Page 168 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 10558 Unsigned / 2 Error status Error status if config‐ ● Bit 0: Overflow (> 25 Read ured to current input.
  • Page 169 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9403 Unsigned / 2 Error status Error status if config‐ ● Bit 0: Overflow Read ured to frequency out‐...
  • Page 170: Peak Values

    MODBUS commands 4.10 Modbus holding registers tables 4.10.8.5 Peak values Process value 1 Table 4-86 Process value 1 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 11200 Unsigned / 2 Process value...
  • Page 171 MODBUS commands 4.10 Modbus holding registers tables Process value 2 Table 4-87 Process value 2 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 11201 Unsigned / 2 Process value Process value config‐...
  • Page 172 MODBUS commands 4.10 Modbus holding registers tables Process value 3 Table 4-88 Process value 3 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 11202 Unsigned / 2 Process value Process value config‐...
  • Page 173 MODBUS commands 4.10 Modbus holding registers tables Process value 4 Table 4-89 Process value 4 Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 11203 Unsigned / 2 Process value Process value config‐...
  • Page 174: Characteristics

    MODBUS commands 4.10 Modbus holding registers tables 4.10.9 Characteristics 4.10.9.1 Product Table 4-90 Product Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6019 Unsigned / 2 CT variant Shows whether or not ●...
  • Page 175: Sensorflash

    MODBUS commands 4.10 Modbus holding registers tables 4.10.10 SensorFlash 4.10.10.1 SensorFlash Table 4-92 SensorFlash Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6164 Unsigned / 2 Installed Shows status of SD ●...
  • Page 176: Data Logging

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6182 Unsigned / 2 Backup Command to overwrite ● 1: Overwrite existing Write on‐...
  • Page 177: Simulation

    MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 11404 Unsigned / 2 Register 1 Modbus register that 65535 Read / defines the parameter write to be logged.
  • Page 178 MODBUS commands 4.10 Modbus holding registers tables Channel 2 output status Table 4-95 Channel 2 output status Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 8864 Unsigned / 2 Simulation Enables or disables...
  • Page 179 MODBUS commands 4.10 Modbus holding registers tables Channel 3 output current Table 4-98 Channel 3 output current Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9125 Unsigned / 2 Simulation Enables or disables...
  • Page 180 MODBUS commands 4.10 Modbus holding registers tables Channel 3 output pulse Table 4-101 Channel 3 output pulse Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9273 Unsigned / 2 Simulation Enables or disables...
  • Page 181 MODBUS commands 4.10 Modbus holding registers tables Channel 4 output current Table 4-104 Channel 4 output current Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9325 Unsigned / 2 Simulation Enables or disables...
  • Page 182 MODBUS commands 4.10 Modbus holding registers tables Channel 4 output pulse Table 4-107 Channel 4 output pulse Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9473 Unsigned / 2 Simulation Enables or disables...
  • Page 183: Process Values

    MODBUS commands 4.10 Modbus holding registers tables 4.10.11.2 Process values Simulate process values Table 4-110 Channel 2 output current Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 2780 Unsigned / 4 Enable simula‐...
  • Page 184: Alarms

    MODBUS commands 4.10 Modbus holding registers tables 4.10.11.3 Alarms Simulate alarms Table 4-111 Simulate alarms Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6229 Unsigned / 2 Simulation Defines mode of alarm Read /...
  • Page 185 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6244 Unsigned / 4 Alarm items 8 Bitwise enabling of Read / alarms in alarm items 8.
  • Page 186: Audit Trail

    MODBUS commands 4.10 Modbus holding registers tables 4.10.12 Audit trail 4.10.12.1 Operating time Table 4-112 Operating time Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6160 Unsigned / 4 Operating time Operating time of the...
  • Page 187 MODBUS commands 4.10 Modbus holding registers tables Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6760 Unsigned / 2 Data type Data type of Modbus ● 0: No entry Read register specified by only...
  • Page 188: Fw Update Change Log

    MODBUS commands 4.10 Modbus holding registers tables 4.10.12.3 FW update change log Table 4-114 FW update change log Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 6900 Unsigned / 2 Newest entry...
  • Page 189: Communication

    MODBUS commands 4.10 Modbus holding registers tables 4.10.13 Communication 4.10.13.1 Service channel Service channel Table 4-116 Service channel Modbus Data type / Parameter Description Default value Value range / Access register Size in bytes [unit] Setting options level (unit register) 9594 Unsigned / 2 USB mode...
  • Page 190 7326 Unsigned / 2 Unique ID code Unique ID code nee‐ Read ded to request a PUK only from Siemens custom‐ er support. 6177 Unsigned / 2 PUK to reset all PINs to Write on‐ default values. FCT030 Modbus (From firmware 4.0)
  • Page 191 Definitions Definitions Acyclic Data – data read over the acyclic communication channel, and this data could take several bus scans to be read. The total amount of time that this process takes is random and therefore acyclic. Baud Rate – the speed of the network in bits per second. Class 1 Master –...
  • Page 192 Definitions A.1 Definitions exchanged between the master and the slave during cyclic data exchange. GSD was also originally the German acronym for Gerätestammdaten. Gateway – A gateway is a device that joins two different networks together. For example, to connect a Modbus device to a PROFIBUS network, a Profibus to Modbus gateway is needed. HART –...
  • Page 193 Definitions A.1 Definitions PROFIBUS DP – DP stands for Decentralized Peripheral and was designed for remote input output devices. This forms the core protocol of PROFIBUS. If PROFIBUS were a book, it would be called PROFIBUS DP. PROFidrive – A chapter in the PROFIBUS book or PROFINET book that adds functions to the core protocol for high speed drive applications.
  • Page 194 Definitions A.1 Definitions FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...
  • Page 195 Index Communication parameters Setup, 20 Access control, 41 Access management, 189 Acknowledge events, 142 Data logging, 176 Active events, 139 Default settings Alarm items, 145 Aerated flow, 61 Assign alarm class, 142 Density settings, 59, 70 Device reset, 188 Diagnostic log, 143 Document history, 7 Documentation Channel 2, 166...
  • Page 196 Index Mass flow settings, 69 FW update change log, 188 Medium temperature settings, 70, 71, 72, 73 General, 165 Modbus General channel 2 settings, 80 Network, 20 General channel 3 settings, 92 Modbus holding registers General channel 4 settings, 108 Access control, 41 General Modbus settings, 33, 39 Access management, 189...
  • Page 197 Index Parameter change log, 186 Zero point adjustment, 62 Process value 1, 170 Automatic, 62 Process value 2, 171 Process value 3, 172 Process value 4, 173 Process value filter masks, 135 Product, 174 Selectable values dependent on the view type, 133 Sensor, 138 Sensor cassette, 138 SensorFlash, 175...
  • Page 198 Index FCT030 Modbus (From firmware 4.0) Function Manual, 06/2018, A5E39931813-AB...