MODBUS commands
4.10 Modbus holding registers tables
Process value 3
Table 4-88
Process value 3
Modbus
Data type /
register
Size in bytes
11202
Unsigned / 2
11298
Float / 4
11300
String / 32
11280
Float / 4
11282
String / 32
11206
Unsigned / 2
172
Parameter
Description
Process value
Process value config‐
ured to be monitored
Maximum value Drag indicator of maxi‐
mum value specified by
Process value (11202)
Maximum value
Shows timestamp of re‐
timestamp
corded maximum value
specified by Process
value (11202)
Minimum value
Drag indicator of mini‐
mum value specified by
Process value (11202)
Minimum value
Shows timestamp of re‐
timestamp
corded minimum value
specified by Process
value (11202)
Reset logging
Command to reset the
drag pointers to the
process value's default
value.
Default value
Value range /
[unit]
Setting options
(unit register)
Disabled
● 3000: Mass flow
● 3002: Volume flow
● 3004: Density
● 3010: Medium
temperature
● 3023: Frame
temperature
● 7950: Corrected
volume flow
● 7871: Fraction A
● 7881: Fraction B
● 7800: Fraction A in %
● 7810: Fraction B in %
● 65535: Disabled
Min. floating
-
point value
[units depend‐
ing on proc‐
ess value]
-
Max. floating
-
point value
[units depend‐
ing on proc‐
ess value]
-
-
-
FCT030 Modbus (From firmware 4.0)
Function Manual, 06/2018, A5E39931813-AB
Access
level
Read /
write
Read
only
Read
only
Read
only
Read
only
Write on‐
ly