Table 3-1 Emu Set Point Temperature Conversions - Compaq RA8000 User Manual

Storage subsystems
Hide thumbs Also See for RA8000:
Table of Contents

Advertisement

Table 3–1 EMU Set Point Temperature Conversions
°C
°F
°C
0
32
10
1
34
11
2
36
12
3
37
13
4
39
14
5
41
15
6
43
16
7
45
17
8
46
18
9
48
19
Table 3–2 Temperature Set Point Rules – EMU Firmware Vers. 1.0 and 1.1
1.
Enter all temperatures in degrees Celsius (°C). Do not use fractions, decimals, or
degrees Fahrenheit (°F).
2.
The EMU set point (sensor_3) temperature must be a minimum of 6°C (11°F)
greater than the highest expected ambient (intake) temperature.
3.
The backplane set points (sensor_1 and sensor_2) must be the same temperature
°C (23°F) greater than the highest expected ambient
and a minimum of 13
temperature. This requires a minimum setting of 7°C (13°F) greater than the EMU
set point.
4.
EMU firmware versions 1.0 or 1.1 cannot use the set emu
sensor_n_setpoint=default command. Instead, the following command is
required:
set emu sensor_n_setpoint=nn
((where nn is the desired temperature in
EK–SMCPR–UG. A01
°F
°C
°F
50
20
68
52
21
70
54
22
72
55
23
73
57
24
75
59
25
77
61
26
79
63
27
81
64
28
82
66
29
84
°C).
387404–001
Chapter 3. Configuring the Storage Cabinet
ºC
°F
°C
30
86
40
104
31
88
41
106
32
90
42
108
33
91
43
109
34
93
44
111
35
95
45
113
36
97
46
115
37
99
47
117
38
100
48
118
39
102
49
120
°F