Service and maintenance
10.3 Firmware update
10.3.2

Update firmware via TIA Portal (STEP 7 Basic / Professional)

This section is intended only for S7 users.
Requirements
● The communications module is connected to the controller or PC via Industrial Ethernet
or PROFINET.
● The communications module has been separated from running operation.
Note that performing the update while the application is running can slow down both the
update and command processing.
● The required update file is stored locally.
Procedure
Proceed as follows to perform a firmware update of the communications module via STEP 7
Basic / Professional (TIA Portal):
1. Start the TIA Portal.
2. Open your existing project and change to the project view.
3. Change to the network view.
4. Right-click on the desired communications module and click on "Online & Diagnostics" in
the shortcut menu.
5. Select the entry "Functions > Firmware Update via Web Interface".
6. Click on the "Web Diagnostics" button.
Reaction: WBM of the communications module opens in your Web browser.
Figure 10-3
Firmware update of the communications module
7. Continue the firmware update as described in the section "Updating the firmware via
WBM (Page 135)".
136
SIMATIC RF185C, RF186C, RF188C
Operating Instructions, 10/2018, C79000-G8976-C512-01