OPERATION
6
Menu No. Function
C3.1.3
Select
Conversion
C3.2 Input Table
C3.2 Input Table
C3.2 Input Table
C3.2 Input Table
C3.2.2
Point
C3.2.4
Level
C3.2.5
Conv. Value
C4 Output
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1.1
Current Out. 1
Var.
C4.1.2
0% Range
90
Function description
If you must make a volume conversion table,
set this menu item to "Volume". If you must
make a mass conversion table, set this
menu item to "Mass". If you must make a
linearization table to make sure that the
readings always agree with reference
measurements, set this menu item to
"Linearization".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
This adds a point on the conversion table.
Each time you enter this menu item, this
number will automatically increment by 1
point. If it is necessary to change the data
for a point, change the point number. When
you push [^ ^ ^ ^ ], you go to menu item C3.2.4
Level.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
Enter the level value for the point given in
C3.2.2. Push [^ ^ ^ ^ ] to confirm the level value
and go to C3.2.5 Conv. Value.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
Enter the conversion value (volume, mass or
linearization) for the point given in C3.2.2.
Push [^ ^ ^ ^ ] to confirm the conversion value
and go back to menu C3.2.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
Make a selection from the available output
functions to scale the current output values.
This is not shown in the Normal mode.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
Give a measurement value to 0% output
(refer also to menu item C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
1 Var
1 Var for the output function). 0% output =
1 Var
1 Var
4 mA. It is possible to have an output less
than 4 mA (<0%) if you set C4.1.4 Current
Out. Range to "3.8-20.5 mA".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
www.honeywellprocess.com
Selection list
Volume, Mass,
Linearization
min-max:
001...050
min-max:
+03
0.0...100.0
mm /
0.0...3937.0¨
min-max:
Volume:
+09
0.0...100.0
m³ /
+12
0.0...26.417
gal
Mass:
+09
0.0...100.0
kg /
+09
0.0...220.46
lb
Linearization:
+12
0.0...100.0
mm /
+12
¨
0.0...3.937
Level, Distance, Sensor
Value, Reflection
2
min-max:
+06
+06
-4.9
...+5.1
mm /
+03
+03
-192.91
...+200.79
/
-16076...+16732 ft
34-VF-25-131 iss.1 GLO Feb 2019 US
RM640
Default
Volume
001
0.0 mm / 0.0¨
Volume:
0.0 m³ / 0.0 gal
Mass:
0.0 kg / 0.0 lb
Linearization:
0.0 mm / 0.0¨
Level
1
0.0 mm
1