OPERATION
6
Menu
Function
No.
B1.1.8
Distance Lin.
B1.1.9
Ullage Volume
B1.1.10
Ullage Mass
84
Function description
This sets the device to a given test
distance value (linearized). This menu
item is only available if you set up a
linearization table in menu item C3.1
Edit Table. Make sure that menu item
Edit Table
Edit Table
Edit Table
C4.1.1 Current Out. 1 Var. is set to "Lin.
Distance" before the device simulates
a linearized distance value. This
procedure sends an output signal that
agrees with the test reading. Output
will change to the selected value,
independent of the measurement data.
When you push [^ ^ ^ ^ ] to confirm the
value, the display shows the question
"Start Simulation?" Push [ ] or [ ] to
set the display to "Yes". Push [^ ^ ^ ^ ] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure: Expert
procedure:
procedure:
procedure:
This sets the device to a given test
ullage volume value. This menu item is
only available if you set up a conversion
(volume) table in menu item C3.1 Edit
Table. Make sure that menu item
Table
Table
Table
C4.1.1 Current Out. 1 Var. is set to
"Ullage Volume" before the device
simulates an ullage volume value. This
procedure sends an output signal that
agrees with the test reading. Output
will change to the selected value,
independent of the measurement data.
When you push [^ ^ ^ ^ ], the display shows
the question "Start Simulation?" Push
[ ] or [ ] to set the display to "Yes".
Push [^ ^ ^ ^ ] again to start the test. The
device goes to back to Normal mode
after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure:
procedure:
procedure: Expert
procedure:
This sets the device to a given test
ullage mass value. This menu item is
only available if you set up a conversion
(mass) table in menu item C3.1 Edit
Table. Make sure that menu item
Table
Table
Table
C4.1.1 Current Out. 1 Var. is set to
"Ullage Mass" before the device
simulates a mass value. This
procedure sends an output signal that
agrees with the test reading. Output
will change to the selected value,
independent of the measurement data.
When you push [^ ^ ^ ^ ] to confirm the
value, the display shows the question
"Start Simulation?" Push [ ] or [ ] to
set the display to "Yes". Push [^ ^ ^ ^ ] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure: Expert
procedure:
procedure:
procedure:
www.honeywellprocess.com
Selection list
min-max:
-5000.0...+5000.0 m /
+03
-196.85
C3.1
C3.1
C3.1
-16404...+16404 ft
min-max:
+06
0...1.00
C3.1 Edit
C3.1 Edit
C3.1 Edit
min-max:
+09
0...10.000
C3.1 Edit
C3.1 Edit
C3.1 Edit
Default
1
+03
...+196.85
in /
1
1
kg
34-VF-25-131 iss.1 GLO Feb 2019 US