Honeywell RM640 Handbook page 83

Non-contact radar level meter - 24 ghz radar (fmcw) level transmitter for solids from granulates to rocks
Table of Contents

Advertisement

RM640
Menu
Function
No.
B1.1.5
Level Lin.
B1.1.6
Volume
B1.1.7
Mass
34-VF-25-131 iss.1 GLO Feb 2019 US
Function description
This sets the device to a given test level
value (linearized). This menu item is
only available if you set up a
linearization table in menu item C3.1
Edit Table. Make sure that menu item
Edit Table
Edit Table
Edit Table
C4.1.1 Current Out. 1 Var. is set to "Lin.
Level" before the device simulates a
level value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [^ ^ ^ ^ ] to confirm the
value, the display shows the question
"Start Simulation?" Push [ ] or [ ] to
set the display to "Yes". Push [^ ^ ^ ^ ] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure: Expert
procedure:
procedure:
procedure:
This sets the device to a given test
volume value. This menu item is only
available if you set up a conversion
(volume) table in menu item C3.1 Edit
Table. Make sure that menu item
Table
Table
Table
C4.1.1 Current Out. 1 Var. is set to
"Volume" before the device simulates a
volume value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [^ ^ ^ ^ ] to confirm the
value, the display shows the question
"Start Simulation?" Push [ ] or [ ] to
set the display to "Yes". Push [^ ^ ^ ^ ] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure:
procedure:
procedure: Expert
procedure:
This sets the device to a given test
mass value. This menu item is only
available if you set up a conversion
(mass) table in menu item C3.1 Edit
Table. Make sure that menu item
Table
Table
Table
C4.1.1 Current Out. 1 Var. is set to
"Mass" before the device simulates a
mass value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
When you push [^ ^ ^ ^ ] to confirm the
value, the display shows the question
"Start Simulation?" Push [ ] or [ ] to
set the display to "Yes". Push [^ ^ ^ ^ ] again
to start the test. The device goes to
back to Normal mode after 1 hour.
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
Minimum access level to do the
procedure: Expert
procedure:
procedure:
procedure:
www.honeywellprocess.com
Selection list
min-max:
-5000.0...+5000.0 m /
+03
-196.85
C3.1
C3.1
C3.1
-16404...+16404 ft
min-max:
+06
0...1.00
C3.1 Edit
C3.1 Edit
C3.1 Edit
min-max:
+09
0...10.000
C3.1 Edit
C3.1 Edit
C3.1 Edit
OPERATION
Default
1
+03
...+196.85
in /
1
1
kg
6
83