11.1.2.9. GETSTATUS
Format:
Limitations:
Description
11.1.2.10.
Format:
Limitations:
Description
CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
GETSTATUS
Can be executed by ATS, administrator or user.
Gets the current status of the device.
The returned data are in the following format:
zones,partitions,outputs,battery_voltage,voltage_AC,0x0,0x0,
blocked_zones
where:
zones – means the current zone status. It is a bit-vector, where bit 1
(counting from 0) means the zone 1 , bit 2 the zone 2, etc. If the zone is
impaired, the bit is set.
partitions – means the current partition status. It is a bit-vector, where bit
0 means the partition 1 and bit 1 the partition 2 (otherwise than for the
zone and outputs where bit 1 means the zone /output 1). If the partition is
armed or counts down the time to output the corresponding bit is set.
outputs – means the current status of outputs. It is a bit-vector, where bit
1 (counting from 0) means the output 1, bit 2 the output 2 and bit 3 the
output 3. If the output is enabled the bit is set.
Battery_voltage – battery voltage in mV (12000 = 12V). If the battery is
not connected, the readings may be incorrect, and be around 9V (9000)
voltage_AC – AC voltage at the AC terminals of CPX200NB (downstream
the transformer) in mV (18000 = 18V)
blocked_zones – means the current status of the zone blockade. It is a bit-
vector, where bit 1 (counting from 0) means the zone 1, bit 2 the zone 2
itd. If the zone is blocked, the bit is set.
GETPARAM
GETPARAM=parameter
Parameter is equal to APN or UN or PW or Server or PORT or SMS or
SMSPERIOD or as id_typu , index, possible to execution only by ATS.
Allows you to retrieve the value of a proper configuration parameter. The
configuration parameters are described in the section on parameters. It is
a twin command with SETPARAM.