System Options - EBS CPX200NB Installation And Programming Manual

Alarm control unit
Hide thumbs Also See for CPX200NB:
Table of Contents

Advertisement

In order to protect the settings against accidental modification, the function is to be
confirmed with installer code. 3 beeps will confirm the successfully entered function. Using
that function will trigger the control unit's reset using default parameters.
You can press

6.6. SYSTEM OPTIONS

That function allow to switch on and switch off additional options of the system. The
argument of the function is BIT type. By pressing 1, 2, 3, 4, 5 and 6 keys, you can switch
on/off proper option. 3 beeps will confirm the successfully entered function.
Where:
Options – number of option (BIT type parameter):
 1 – Enable faults memory indication – when is switched off, LED SYSTEM does not
show by blinking the faults that are not active; you can display inactive faults by
choosing "faults memory" user function.
 2 – Disable ATS monitoring. If his option is enabled, ATS failure isn't signaled to the
user in any way on the keypad and it doesn't cause arm prevention.
 3 – Disable automatic arm prevention overriding when fault. If this option is disabled
and at least on fault is active in the system, arm prevention isn't signaled to the user
during partition arming. Instead arm prevention is automatically overridden. If option
is enabled, faults causes arm prevention which can be overridden by user.
 4 – Access to alarm and fault memory requires authorization. If this option is
enabled, checking alarm memory and fault memory is available only after a user code
is entered. This option must be enabled in order to comply with EN 50131 standard
requirements for Grade 2.
 5 – Alarms and inputs interlocking states are not displayed. If this option is
enabled,.alarms and line state are not displayed on the keypad. This option must be
enabled in order to comply with EN 50131 standard requirements for Grade 2.
 6 – Temporary keyboard lock after three access failures. If this option is enabled, the
keypad will be blocked for 90 seconds, after entering an invalid code three times.
After this period, another lock will occur after entering a wrong code three times. The
counter of invalid codes will be reset after a correct code is entered (e.g. after
entering invalid code two times). This option must be enabled in order to comply with
EN 50131 standard requirements for Grade 2.
 7 – Use duress code. Duress code is used to inform the monitoring station about a
distress event. Each user has his own duress code.
NOTE: Firmware versions older than 2.1.0 do not support the duress
code. Upgrading the Firmware to version 2.1.0 or newer one has to
make sure that there are no conflicts between existing users and
their duress codes.
CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
<Installer code>
any time to exit without saving changes.
<Options>