Users Remote Management; Zones Configuration - EBS CPX200NB Installation And Programming Manual

Alarm control unit
Hide thumbs Also See for CPX200NB:
Table of Contents

Advertisement

 8 – Show partition arming mode instead of inputs interlocking states. By default
systerm will show violated and interlocked zones on diodes 1-8. Setting this option
will tell the system to show partitoin armind mode on diodes 1-2. Zones states will no
longer be available.
Display scheme:
Led off – partition disarmed
Led on – partition armed in away mode
Led blinking – partition armed in stay mode
You can press

6.7. USERS REMOTE MANAGEMENT

That function allow to switch on or switch off remote users management. The argument of
the function is BIT type. By pressing key 1, you can switch on/off option. 3 beeps will
confirm the successfully entered function.
Where:
Options – number of option (BIT type parameter):
 1 – Users remote management enable – when is swiched on
You can press

6.8. ZONES CONFIGURATION

The zones can be configured using complex service functions, after activation of which, all
the parameters related to the relevant zone can be given subsequently or in a form of series
of service functions that configure one zone-related parameter.
Codes of zone configuration functions are defined as per the following pattern:
where:
XX –
determines the number of zone from 01 to 07; entering number 00 will change the
parameters for all zones in the system,
Y
– number of parameter related to a given zone:
 0 – complex function, the initiation of which configures the parameters listed below
as another set of parameters;
1 – type of zone response (DEC type parameter):
o 0 – instant
o 1 – delay
o 2 – 24h burglary
o 3 – arming/disarming
o 4 – 24h tamper
o 5 – interior delayed
o 6 – 24h burglary silent
o 7 – 24h fire
CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
any time to exit without saving changes.
any time to exit without saving changes.
<XX> <Y>
<Options>
32 / 116