Inputs / Outputs; Zones - EBS CPX200NB Installation And Programming Manual

Alarm control unit
Hide thumbs Also See for CPX200NB:
Table of Contents

Advertisement

8.3. INPUTS / OUTPUTS

The alarm control unit has 7 configurable zones and 3 software controlled outputs. Zones
can be freely divided into two partitions. Each of zones and outputs has a number of
programmable parameters defined below.
8.3.1.

Zones

8.3.1.1. Zone mode
The parameter allows for determining the stable input line state. Any change of that
state causes alarm message to be sent. Input can be NC or NO type. The following
configuration types are available: NC / NO / EOL-NC / EOL-NO / DEOL-NC / DEOL-
NO. NC type input must be closed for the whole time. Line interruption causes its
induction. NO type input remains open. It activates when closed. EOL and DEOL (with
parameters or double parameters assigned) differ with 1 or 2 resistors allowing
distinguishing alarm from sabotage. Electric diagrams for all configuration types were
described in chapter 3.4.
8.3.1.2. Response type
 Instant – disruption of the line causes immediate alarm, if the system is armed.
 Delay – that type of line is usually used for detectors operation at the facility
entries. The line switches into alarm state after the expiration of programmed
CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL
62 / 116