Siemens Sicam P855 7KG85 Series Device Manual page 226

Power monitoring device and power quality recorder
Table of Contents

Advertisement

8 Operation at Use of the Display
8.4 Parameterization
Table 8-3
Parameter
Use PTs:
V primary
Primary rated voltage Ph-Ph
Use PTs:
V secondary
Secondary rated voltage Ph-
Ph
Rated value
Use CTs?
Use CTs:
I primary
primary rated current
Use CTs:
I secondary
secondary rated current
Zero-point suppression
(in % of Vrated
and Irated)
226
Basic Parameter Settings (cont.)
Default Setting
AC 10,000.00 V
AC 100 V
AC 5 A
No
(no checkmark)
AC 1,000.00 A
AC 1.00 A
0.3 %
AC 100.00 V to 1,000,000.00 V
AC 1.0 V to 1000.0 V
Current Inputs
AC 1 A
AC 5 A
Yes (checkmark)
No (no checkmark)
AC 1.0 A to 100,000.0 A
AC 0.01 A to 10 A
Zero-Point Suppression
0.0 % to 10.0 %
Setting Range
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018