15 Operating Parameters
15.4 Recording and Reporting
15.4
Recording and Reporting
15.4.1
Event Recorders
Parameter
Swell threshold
Dip threshold
Interruption threshold
Event hysteresis
Underfrequency threshold
Overfrequency threshold
Voltage unbalance threshold
15.4.2
Trigger Management
Parameter
Trigger active
Tolerance unit
Lower threshold
Upper threshold
294
Default Setting
Supply Voltage
110 %
90 %
5 %
2 %
Frequency
1 %
1 %
Unbalance
5 %
Default Setting
Voltage trigger limits
no
Percentage
90.00 %
of the of the primary nominal
voltage
110.00 %
of the of the primary nominal
voltage
Setting Range
105 % to 140 % in 5-% steps
75 % to 95 % in 5-% steps
1 %, 2 %, 3 %, 5 %, 8 % 10 %
1 % to 6 % in 1-% steps
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
1 % to 5 % in 1-% steps
Setting Range
no
yes
Percentage
Numerical
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
100.0 % to 10 000.0 % of the primary
nominal voltage
0.0 V to 1 000 000.0 V
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018