Siemens Sicam P855 7KG85 Series Device Manual page 295

Power monitoring device and power quality recorder
Table of Contents

Advertisement

Hysteresis
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
Total recording duration
Pretrigger ratio
Record ph-ph voltage
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
2.00 %
of the of the primary nominal
voltage
Current trigger limits
no
Percentage
90.00 %
of nominal current In
110.00 %
of nominal current In
2.00 %
of nominal current In
Waveform capture setting
2.0 s
10 %
no
15 Operating Parameters
15.4 Recording and Reporting
0.0 % to 50.0 % of the of the primary
nominal voltage
no
yes
Percentage
Numerical
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
0.0 % to 50.0 % of of nominal current In
0.2 s to 3.0 s in 0.2-s steps
0 % to 30 % in 5-% steps
no
yes
295

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sicam p850 7kg85 series

Table of Contents