10.2
Calibrating the Alternating Voltage Measuring Range
Measurement Setup
Figure 10-1
NOTE
Calibration is only possible with symmetrical phases (3 x 120°).
Measuring Ranges
You can perform the calibration for the following alternating voltage measuring ranges:
•
AC 63.5 V
•
AC 110 V
•
AC 230 V
•
AC 400 V
Calibration
To calibrate the alternating voltage measuring ranges, proceed as follows:
✧
Set up the measurement as shown in figure 10-1, depending on the device variant.
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Measurement Setup for Calibrating the Alternating Voltage Measuring Range
10.2 Calibrating the Alternating Voltage Measuring Range
Reference
Voltage
Output
1
2
3
N