4.1.2.4 Event Recorder (Only SICAM P855)
The Event Recorder exclusively records PQ events (undervoltage, overvoltage, voltage interruptions). The use
nominal voltage is the reference value for the analysis.
V
[%]
rated
110
108
100
92
90
Figure 4-6
Voltage Event
Dip threshold:
Swell threshold:
Voltage interruption threshold:
Event hysteresis:
Frequency Event
Underfrequency threshold:
Overfrequency threshold:
Voltage Unbalance Event
Voltage unbalance threshold:
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Voltage dip
Event
Event
start
stop
Duration of
event
Recording of the Event Recorder, Overvoltage and Undervoltage
75 % to 95 % (default 90 %)
105 % to 140 % (default 110 %)
1 % to 10 % (default 5 %)
1 % to 6 % (default 2 %)
0.1 % to 5 % (default 1 %)
0.1 % to 5 % (default 1 %)
1 % to 5 % (default 5 %)
Voltage swell
Hysteresis
(2 %)
Hysteresis
(2%)
Event
Event
start
stop
Duration of
event
4 Measurands and Recording
4.1 Measuring and Recording System
t
t
39