Page 3
Additional Support Should further information on the System SICAM be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens represen- tative. Our Customer Support Center provides a 24-hour service.
Page 4
• The limiting values stated in the document must not be exceeded. This must also be considered during testing and commissioning. ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563- , Release Date...
1.1 Introduction Introduction SICAM P37 3-phase harmonic power meter integrates measurement, record, power metering, remote communication and control, large screen LCD and network communication functions. It is designed for measuring power grid parameters such as voltage, current, power, power factor and frequency and active and reactive energy.
Functions Measurement Energy Metering Limit violation Alarm Display and Buttons Communication Permission and Security Management Digital Input and Output Interface SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
• Total harmonic voltage distortion and total harmonic current distortion of each phase - Total harmonic voltage distortion: - Total harmonic current distortion: • Voltage wave crest factor (CF) of each phase, indicating peak of distorted waveform SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
• total fundamental active power and total harmonic active energy • supply active energy of each phase, combined reactive energy of each phase, fundamental active energy and harmonic active energy of each phase SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Use MODBUS RTU protocol to set alarm parameter: set 0110 address to "07", 0111 to "0000", 0112 to "5DC0" (multiply "240" by 100 to generate "24,000" and convert it into "00005DC0"), 0113 to "00" and 0114 to "02". SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
(factory default 60 minutes). Error count will be reset after setting once using correct password if such count is less than specific limit. Error count of password and lock time can be set (available in factory state). SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
This product is provided with 4-digit binary inputs interface based on passive dry contact. Terminals are identi- fied as DI1, DI2, DI3, DI4 and COM. COM is the common terminal. Figure 3-2 Circuit Diagram of Binary Input Interface SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 19
This product is provided with two relay outputs interfaces for alarm indication or protection control output in many conditions. Electric parameter of internal relay: AC 250 V/DC 30 V, 3 A. Figure 3-3 Circuit Diagram of Relay Output Interface ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 20
Functions 3.7 Digital Input and Output Interface SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Code list of optional settings in area A: Data item Data type (current value) Data item Data type (current value) Transient Maximun Minimum Transient Phase voltage Voltage distortion rate Line voltage Current distortion rate SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 23
Net reactive power Frequency Error code Note In flip-with-key state or parameter-set-with-key state, this product will automatically return to cyclic display state if no key operation within defined duration. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
(27) (31) Phase (04) (08) (12) (16) (20) (24) (28) (32) Frequency (33) Version (34) Active con- (35) stant Reactive (36) constant Device ID (37) Error code (38) SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 25
When area A is selected, press "▲" or "▼" to enter zero sequence current display mode. In the figure, L1=0.940 A, L2=1.003 A, L3=1.006 A and zero sequence current=0.079 A. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 26
At cyclic display mode, press "▲" or "▼" to enter key display mode. When area A is selected, press "▲" or "▼" to enter phase angle items. In the figure, L1=30.0°, L2=30.2°, L3=31.0°. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 27
At cyclic display mode, press "▲" or "▼" to enter key display mode, press " " to switch to area B, and press "▲" or "▼" to switch to current Phase B total active power items. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 28
At cyclic display mode, press "▲" or "▼" to enter key display mode, press " " to switch to area B, and press "▲" or "▼" to switch to reactive pulse constant items. In the figure, reactive constant=5,000 imp/kWh. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 29
" once after adjusting parameters with "▲" and "▼" to display "Sure", and press " " once again to alter parameters. Pressing " " immediately after "Sure" appears will cancel current alteration. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 30
3P3L_2CT 3phase3wire -2CT Wiring mode 3P3L_3CT 3phase3wire -3CT System AUto auto setting 6 bits in total, Set L0-2 password Password Default setting: 000000 Clearing extreme value Meter reset SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 31
The meter should be reset after altering PT/CT ratio to ensure reasonable correspondence between communication reading and displayed metering data. 3. Parameter setting with keys (take "Conn communication setting" for example) Figure 4-2 Parameter setting with keys SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 32
". Press " " once again to activate new parameter. Pressing " " at any time during parameter setting will cancel setting or return to previous menu. ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Installation and Wiring Total Dimension Precautions of Installation Terminals and Wiring Diagram SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
6. Requirement for electric connection: In voltage input circuit and operating power supply circuit, appropriate fuses (such as 0.5 A fuse) should be connected and a CT short-circuit box should be provided to prevent open circuit of CT wiring. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
For cables to be connected to upper and lower main terminals, cold-pressed UT2.5-3 terminal is recommended before connection. The diagram of connection is below. Figure 5-2 Connection Diagram of Main Terminal SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 36
DC/AC input, with input voltage 40 V to 420 V. For 3-phase-3-wire connection, V and V should be con- nected together, see Figure 5-5. Figure 5-3 Wiring Diagram of 3-phase-4-wire (W/O PT) SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 37
Installation and Wiring 5.3 Terminals and Wiring Diagram Figure 5-4 Wiring Diagram of 3-phase-4-wire (With PT) Figure 5-5 Wiring Diagram of 3-phase-3-wire ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 38
Installation and Wiring 5.3 Terminals and Wiring Diagram SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Communication Use of Communication Introduction of MODBUS-RTU Communication Protocol SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
4. Shield Twisted Pair should be used for RS485 bus cable. For two twisted pairs, different colors are recom- mended, one color for "A" side and another color for "B" side of 485 communication port. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
CRC will avoid data distortion during responsive transmission of master and slave and improves security and efficiency of system. For formation rule of check code, see Annex 1. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
10 H 00 H 03 H 00 H 02 H 04 H 00 H BC H 61 H 4E H Low check High check address - Response frame Device address 10 H 00 H 03 H 00 H 02 H Low check High check SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Repeat step 3 and step 4 until shift rightwards 8 times. Now, all 8-bit data are processed. • Repeat step 2 to step 5 to process next 8-bit data. • The CRC register derived finally is CRC. SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
"alarm manner control byte" is 0 or 1 High byte: binary input status (note) Binary inputs 0102 H unsigned int 2 bytes Low byte: binary output status SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 45
10 bytes See Alarm 1 ...0123 H 0124 H Alarm 5 10 bytes See Alarm 1 ...0128 H 0129 H Alarm 6 10 bytes See Alarm 1 ...012D H SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 46
Low bytes BIT0 and BIT1 respectively mean status of relay output 1 and 2. Bit value 0 means contact is open (relay no operation) while 1 means contact is closed (relay closed). SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 47
2 bytes -32767...32767 Total active power 1010 H signed int 2 bytes -32767...32767 Phase A reactive power 1011 H signed int 2 bytes -32767...32767 1 var SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 48
Phase C fundamental 1202 H unsigned int 2 bytes 0...65535 0.001 A current Phase A 2 harmonic 1203 H unsigned int 2 bytes 0...65535 0.001 A current SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 49
Phase B current 50 1494 H unsigned int 2 bytes 0...10000 0.01% harmonic ratio Phase C current 50 1495 H unsigned int 2 bytes 0...10000 0.01% harmonic ratio SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 50
16 bits Phase A export active 2100 H power high 16 bits unsigned 4 bytes 0...4294967295 0.1 Wh long Phase A export active 2101 H power low 16 bits SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 51
0...65535 1 var Phase B reactive power 4X69 unsigned int 0...65535 Phase C reactive power 4X70 unsigned int 0...65535 Total reactive power 4X77 unsigned int 0...65535 SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Page 52
0...65535 Note X-0 means maximum value while X=1 means minimum value. This manual applies to software version for 150113 and later released by the device. ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
The meter should be stored in clean location free of hazardous substances or gas which may cause corrosion in air. • In the operating environment of the meter, lightning protection should be provided. ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...
Ordering Number Model: SICAM — P Function 3U, 3I, P, Q, PF, f, kwh, kVarh, 2 pulse, Harmonic, 4BI, 2BO, 1*RS485 Model Ordering No. SICAM P37 7KG7331-1HA11 ■ SICAM P37, 3-phase Harmonic Power Meter, User Manual E50417-H8940-C563-4, Release Date 06.2018...