5 Getting Started
5.7 Commissioning
DIN Rail Devices
Press the IP-Addr. push-button on the DIN Rail Site for at least 3 s.
Figure 5-7
When you press the IP-Addr. push-button, SICAM P850/P855 will reset and use the default IP address
until you have set a new IP address or switched the device off and on again.
NOTE
Changing the IP address will lead to a device reset, and the LEDs indicate that the device was started with the
default IP address (see chapter 12.3).
In this case, the parameterized IP address and the default IP address are displayed on the Information tab,
Device information item (see chapter 7.2.8).
When the device has started with the default IP address, the factory-set default passwords are also active (see
chapter 7.3.6.5).
84
Location of the Push-button for Activating the Default IP Address
IP-Addr. push-button for
default IP address
Default IP Address: 192.168.0.55
Default Subnet Mask: 255.255.255.0
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018