Messages - gefran ADV200 Series Quick Start Up Manual, Specification And Installation

Field oriented vector ac drive for synchronous/asynchronous motors
Hide thumbs Also See for ADV200 Series:
Table of Contents

Advertisement

8.2 Messages

Note !
For more information see
Index
Error message shown
on the display
1
Load default param
2
Option detect slot 1
3
Option detect slot 2
4
Option detect slot 3
5
Autotune
128
chapter
6.7.
Sub-code
Condition: may occur during loading of the parameter database saved in flash
normally appears in the following conditions: at initial power-on when a new firmware version is
downloaded, when the regulation is installed on a new size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has
occurred in the parameter database saved in Flash.
If this message is displayed the drive restores the default database, i.e. the one downloaded.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution: Set the parameters to the value required and perform Save parameter
Condition: at power-on, the drive recognizes the presence of an optional card in one of the three
expansion slots.
One of the three messages is shown on the display
0H-0
None
0004H-4
Can/DeviceNet
00FFH-255
Unknown
0104H-260
Profibus
0204H-516
Rte
0208H-520
Enc 3 EXP-SESC- I1R1F2-ADV
0301H-769
I�O�1
0308H-776
Enc 4 EXP-EN/SSI- I1R1F2-ADV
0408H-1032
Enc 5 EXP-HIP- I1R1F2-ADV
0608H-1544
Enc 1 EXP-DE-I1R1F2-ADV
0701H-1793
I�O�2
0108H-1800
Enc 2 EXP-SE-I1R1F2-ADV
0808H-2056
Enc 7 EXP-DE-I2R1F2-ADV
0901H-2305
I�O�3
0D01H-3329 I�O�4
0508H-1288
Enc 6 EXP-RES-I1R1-ADV
908H-2312
Enc 8 EXP-ASC-I1-ADV
Solution:
Condition: this may occur during the Autotune procedure
0
No error
The commands are not configured in Local mode.
1
Solution: Execute the requested configuration
The Commands local sel parameter has not been configured from the keypad
2
Solution: Execute the requested configuration
The motor plate data parameters have changed but the Take parameters com-
mand, PAR 2020, has not been executed
3
Solution: Execute the Take parameters command.
ADV200 • Quick start up guide
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Adv200-...-dc series

Table of Contents