9 - Specification
9.1 Environmental Conditions
Installation location ������������������Pollution degree 2 or lower (free from direct sunligth, vi-
Installation altitude ������������������Max 2000m (6562 feet) above sea level (up to 1000m
Mechanical conditions for installation ���Vibrational stress: EN 60721-3-3 Class 3M1
Operating temperature ��������������-10...+40°C (32°...104°F)
Operating temperature (1) ������������+40 ... +50°C with derating, (+104 ... +122°F with
Air humidity (operating) ��������������from 5 % to 85 % and from 1 g/m
Air pressure (operating) [kPa] ����������86 to 106 (class 3K3 as per EN50178)
(1)
The drive is suitable for use under the environmental service conditions (climate,
mechanical, pollution, etc.) defined as usual service conditions according to
EN61800-2.
Attention
9.2 Standards
Directive EC ________________________LVD 2014/35/EU, EMC 2014/30/EU, RoHs 2011/65/EU
Climatic conditions ������������������EN 60721-3-3
Electrical safety ��������������������EN 50178, EN 61800-5-1, UL508C, UL840 degree of
Operating safety ��������������������(for ADV200...+SI series) IEC EN 61800-5-2 , SIL 3 ;
Vibration ��������������������������EN 60068-2-6, test Fc.
Shock ����������������������������EN60068-2-27
EMC compatibility �������������������EN61800-3 EN61800-3 (EMC conducted: immunity and
Protection degree �������������������IP20, ≥ size 7: IP00
Approvals �������������������������
9.3 Accuracy (Asyncronous)
9.3.1 Current control
Type ������������������������������Flux vector CL (Field Oriented Control with feedback) and
134
In menu 4 - DRIVE CONFIG set the Ambient temperature parameter, PAR 564, to 1 (50°C).
10 % derating of output current.
ADV200 • Quick start up guide
bration, dust, corrosive or inflammable gases, fog, vapour
oil and dripped water, avoid saline environment)
without current derating).
derating)
moisture condensation or icing (class 3K3 as per
EN50178)
pollution 2
ISO EN 13849-1 , PL "e"
emissions)
Immunity: environment 2, EN12016
Conducted emission: environment 2, category C2 and C3,
EN12015
Radiated emission: determined by cabinet of final applica-
tion
L
,
Flux vector OL (Open Loop Field Oriented Control)
to 25 g/m
without
3
3
L