Error message shown
on the display
20
Param error
21
Encoder error
22
Options cfg changed
Autotune
23
(phasing)
(Only Synchronous)
132
Sub-code
Condition: if an error occurs during activation of the parameter database saved in flash; the alarm
is inserted in the alarm list and alarm log.
XXX0H-X
The code XXXXH-X indicates the IPA of the parameter that has been set outside the
range allowed when the database is enabled.
Solution: Set the parameter causing the error to a value within the range and run Save param-
eters. Switch the drive off and then switch it back on again.
If the IPA of the parameter is not shown in the manual, contact the service centre.
Condition: this condition may occur when the drive is powered during encoder setup each time
parameter 552 Regulation mode is set.
100H-2564
Cause: An error occurred during setup; the information received from the encoder
is not reliable. If the encoder is used for feedback the Speed fbk loss [22] alarm is
also generated.
Solution: Take the recommended action for the Speed fbk loss[22] alarm.
200H-512
Cause: The firmware on the optional encoder card is incompatible with that on the
regulation card. The information received from the encoder is not reliable
Solution: Contact Gefran in order to update the firmware on the optional encoder card.
Condition: this may occur when powering the drive if an expansion card has been removed or
replaced or the incorrect enable key is inserted for a given firmware function.
0064H-100
Card removed from slot 1
0014H-20
Card removed from slot 2
0003H-3
Card removed from slot 3
0078H-120
Card removed from slot 1 and from slot 2
0067H-103
Card removed from slot 1 and from slot 3
0017H-23
Card removed from slot 2 and from slot 3
007BH-123 Card removed from slot 1, from slot 2 and from slot 3
Solution: Check the hardware configuration, then press ESC. Save the parameters (Save param-
eters, menu 04.01 par 550) to save the new hardware configuration.
0
No error
The encoder card in use cannot manage automatic phasing.
40
Solution: Use the appropriate encoder card
Incorrect Incremental encoder impulse count
41
Solution: Check the electric signals of the incremental encoder. Check the value of
the encoder impulse parameter
Incorrect absolute encoder impulse count
42
Solution: Check the electric signals of the absolute encoder. Check the configura-
tion of the absolute encoder
Incorrect incremental encoder impulse count or incorrect absolute encoder impulse
count probably caused by an incorrect value of the pole pairs parameter or a load
43
applied to the motor.
Solution: Check the value of the pole pairs parameter, check whether a load is
applied
Incorrect incremental encoder impulse count probably caused by the incorrect value
of the encoder impulse parameter.
44
Solution: Check the electric signals of the incremental encoder. Check the value of
the encoder impulse parameter.
Incorrect absolute encoder impulse count
45
Solution: Check the electric signals of the absolute encoder. Check the configura-
tion of the absolute encoder.
ADV200 • Quick start up guide