Error message shown
on the display
11
Load def plc
12
Plc cfg error
13
Plc 1
14
Plc 2
15
Plc 3
16
Plc 4
17
Option bus fault
18
Key failed
19
Key expiring
Sub-code
Solution: Remove the optional cards from the incorrect slots and insert them in the correct slots
Condition: may occur during loading of the parameter database saved in the Flash of the Mdplc
application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the drive is already operating, this means that a problem has
occurred in the parameter database saved in Flash.
If this message appears the drive restores the default database, i.e. the one that was downloaded.
0001H-1
The database saved is not valid
Solution: Set the parameters to the value required and perform Save parameter
Condition: may occur during loading of the Mdplc application
The Mdplc application present on the drive is not run.
0004H-4
The application downloaded has a different Crc on DataBlock and Function table
0065H-101
The application downloaded has an invalid identifier (Info)
0066H-102
The application downloaded has an incorrect task number (Info)
0067H-103
The application downloaded has an incorrect software configuration
0068H-104
The application downloaded has a different Crc on DataBlock and Function table
0069H-105
A Trap error or System error has occurred.
The drive automatically performs a Power-up operation.
The application is not run.
See in Alarm List for further information regarding the error occurred
006AH-106
The application downloaded has an incorrect identifier (Task)
006BH-107
The application downloaded has an incorrect task number (Task)
006CH-108
The application downloaded has an incorrect Crc (Tables + Code)
Solution: Remove the Mdplc application or download a correct Mdplc application
Reserved messages and dedicated to the PLC application. See the application manual.
Condition: this may occur when the drive is turned on, during fieldbus card setup. Error during
configuration or communication error.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is 0, the error regards a
communication problem.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is other than 0, the error
regards a configuration problem.
Solution: For configuration errors, check the configuration of the bus communication, type of bus,
baudrate, address, parameter setting.
For communication errors, check wiring, termination resistors, disturbance immunity, timeout
settings.
For further details, please refer to the user guide for the specific bus.
Condition: this may occur when powering the drive, if the incorrect enable key is inserted for a
given firmware function.
0001H-1
Incorrect PLC key. PLC application not available.
Solution: Ask Gefran to supply the correct key to enable the desired firmware function.
Condition: this may occur at drive power-on if the incorrect enabling key was inserted for a given
firmware function. At this stage the firmware function can still be used freely, but this time limit is
about to expire.
xxxxH-x
Number of hours for which the function can still be used freely.
Solution: Ask Gefran for the correct key to enable the desired firmware function.
ADV200 • Quick start up guide
Description
131