Charger Settings Menu

The Charger Settings menu provides options for configuring the
Freedom SW 230V to operate from your battery bank.
FSW3524 00: Chg Settings
Batt Type
[Flooded]
Custom Settings
Batt Capacity
[440Ah]
Max Chg Rate
[100%]
Charge Cycle
[3-Stage]
ReCharge Volts
[25.0V]
Absorb Time
[180min]
Auto Recharge
[Enabled]
Default Batt Temp
[Warm]
Figure 29 Charger Settings Menu Screen
975-0696-01-01
[*Flooded] [Gel] [AGM] [Custom]
[*3-Stage] [2StgNoFloat]
[*Enabled] [Disabled]
[*Warm] [Hot] [Cold]
Follow procedures on "To select and change a
configurable setting:" on page 38 to change the settings.
Configuring the Freedom SW using the SCP
Table 10 Setting Defaults and Ranges
Model
Freedom SW 230V
Item
Default
Batt Type
Flooded
Flooded, Gel,
Batt Capacity
440Ah
50Ah
Freedom SW 2524-230
Batt Capacity
440Ah
Freedom SW 3524-230
Max Chg Rate
100%
Charge Cycle
3Stage
ReCharge Volts
25.0V
22.0V
Absorb Time
180min
1min
Auto ReCharge
Enabled
Default Batt
Warm
Hot, Warm, Cold
Temp
Min
Max
AGM, Custom
2000Ah
10%
100%
3Stage,
2StgNoFloat
27.0V
480min
Enabled,
Disabled
51