Configuring the Freedom SW using the SCP

Stacking Configuration Menu

The Stacking menu configures the Freedom SW 230V to operate
as a part of a multi-unit installation.
g
Dev Name
[00]
Dev Number
[01]
Stack Mode
[Master]
AC In
[SHORE1]
Battery
[Batt1]
Figure 33 Stacking Menu Screen
IMPORTANT:
Accessing this menu automatically places the Freedom SW
230V in standby mode. When entering the Stacking menu, the unit
identifies itself by flashing all front panel lights. After exiting the Stacking
menu, the Freedom SW 230V returns to operating mode and the front panel
lights stop flashing.
NOTE:
The same Battery number must be used for all stacked Freedom
.
SW 230V units
When installing a stacked system, every setting on the Stacking
menu (except for Dev Name) must be configured for each Freedom SW
230V in the system. The settings should be configured in the following
order:
Dev Number
Stack Mode
58
[*Master] [Slave] [L2Master]
[*SHORE1] [SHORE2 to 5] [GEN1 to 5] [None]
Follow procedures on "To select and change a
configurable setting:" on page 38 to change the settings.
Table 17 Stacking Menu Description and Values
Item
Description
Allows the customizing of the
Dev Name
default name for the inverter/
charger. This setting is
optional and does not affect
operation. See "Setting the
Device Name" on page 59.
Allows setting of a unique unit
Dev Number
number in a multiple-unit
system. See "Setting the
Device Number" on page 60.
Parallel Stacking: For this to
Stack Mode
operate, one Freedom SW
230V must be configured to
Master and the other as
Slave, otherwise a system-
wide fault is asserted.
Identifies to the system the
AC In
kind of AC input the
inverters are accepting.
Points the system to which
Battery
battery bank is used.
a. Applies to all Freedom SW 230V models.
b. L2Master is not supported in Freedom SW 230V models.
a
Default
Range
FSW3524E in the
Can be changed by
case of Freedom
the user.
SW 3524-230.
00
00–31
Master
Master,Slave,
L2Master
SHORE1
SHORE1–SHORE5
GEN1–GEN5
NONE
Batt1
Batt1–Batt5
Freedom SW 230V Owner's Guide