Danfoss VLT HVAC Basic Drive FC 101 Programming Manual page 84

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Parameters
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range:
0 V
[0 - 65535 V]
*
3
3
16-34 Heatsink Temp.
Range:
0 °C
[-128 - 127 °C] View the heat sink temperature of the
*
16-35 Inverter Thermal
Range:
0 %
[0 - 255 %] View the percentage of thermal load on the
*
16-36 Inv. Nom. Current
Range:
0 A
[0 - 655.35 A] View the inverter nominal current. The data
*
16-37 Inv. Max. Current
Range:
0 A
[0 - 655.35 A] View the inverter maximum current. The
*
16-38 SL Controller State
Range:
0
[0 - 20 ] View the actual state of the smart logic controller
*
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
0 %
[-200 - 200 %] View the total reference, the sum of
*
16-52 Feedback[Unit]
Range:
0
ProcessCtrlUnit
82
Function:
Shows the actual DC-link voltage.
Function:
frequency converter.
Function:
frequency converter. At 100%, a trip occurs.
Function:
is used for motor overload protection and
so on.
Function:
data is used for calculation of frequency
converter protection and so on.
Function:
(SLC).
Function:
digital, analog, preset, bus, and freeze
references.
Function:
[-4999 - 4999
View the feedback resulting
ProcessCtrlUnit]
from the selection of scaling
*
in parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Danfoss A/S © 04/2018 All rights reserved.
®
VLT
HVAC Basic Drive FC 101
16-54 Feedback 1 [Unit]
Range:
0
ProcessCtrlUnit
16-55 Feedback 2 [Unit]
Range:
0
ProcessCtrlUnit
3.12.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
0
[0 -
*
4095 ]
16-61 Terminal 53 Setting
Option:
[0]
Current mode
*
[1]
Voltage mode
16-62 Analog input 53
Range:
1
[0 - 20 ]
*
Function:
[-999999.999 -
View the feedback 1 value
999999.999
resulting from the selection
*
ProcessCtrlUnit]
of scaling in
parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Function:
[-999999.999 -
View the feedback 2 value
999999.999
resulting from the selection
*
ProcessCtrlUnit]
of scaling in
parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Function:
View actual state of the digital inputs 18, 19, 27,
and 29.
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input terminal 29
Bit 3
Digital input terminal 27
Bit 4
Digital input terminal 19
Bit 5
Digital input terminal 18
Bit 6–15
Unused
Table 3.8 Bits Definition
Function:
View the setting of input terminal 53.
Current = 0
Voltage = 1
Function:
View the actual value at input 53.