Event code
Event name
74B00000 hex
SF_TwoHandCo
ntrolTypeIII Error
 Other Errors
Event code
Event name
10500000 hex
NX Bus Commu-
nications Settings
Read Error
10510000 hex
Safety Applica-
tion Data Read
Error
10520000 hex
NX Bus Commu-
nications Settings
and Safety Appli-
cation Data Mis-
match
10530000 hex
Non-volatile
Memory Access
Error
80220000 hex
NX Message
Communications
Error
951E0000 hex
Sysmac Studio
Communications
Connection Time-
out
951F 0000 hex
Clear All Memory
Rejected
 User Access Log
Event code
Event name
90400000 hex
Event Log
Cleared
90430000 hex
Memory All
Cleared
NX-series Safety Control Unit User's Manual (Z930)
Meaning
Assumed cause
An error was
Refer to information on the diag-
detected in exe-
nostic code that is given for
cution of a safety
attached information 1 in the
function block.
NX-series Safety Control Unit
Instructions Reference Manual
(Cat. No. Z931)
Meaning
Assumed cause
There is an error
• A hardware failure occurred in
in the NX bus
the non-volatile memory.
communications
• Power was turned OFF while
settings that are
saving data to the non-volatile
saved in non-vol-
memory.
atile memory.
There is an error
• A hardware failure occurred in
in the safety
the non-volatile memory.
application data
• Power was turned OFF while
that is saved in
saving data to the non-volatile
non-volatile
memory.
memory.
There is an error
• The NX bus communications
in the safety
settings that were transferred
application data
to the Safety CPU Unit do not
that is saved in
match the safety application
non-volatile
data.
memory.
Reading/writing
Non-volatile memory failed.
non-volatile
memory failed.
An error was
• The message communications
detected in mes-
load is high.
sage communi-
• The communications cable is
cations for an NX
disconnected or broken.
Unit and the mes-
• Message communications
sage frame was
were cut off as the result of
discarded.
executing a synchronization or
restoration operation on the
Sysmac Studio or as the result
of disconnecting an EtherCAT
slave.
A communica-
• The communications cable
tions timeout
was disconnected.
occurred
between the Sys-
mac Studio and
the Safety CPU
Unit.
Clearing all of
• The Clear All Memory opera-
memory failed.
tion was performed for the
entire Slave Terminal.
Meaning
Assumed cause
The event log
The event log was cleared by the
was cleared.
user.
The Unit settings
The Clear All Memory operation
were cleared.
was performed.
9 Troubleshooting
Level
Maj
Prt
Min
Obs
Info
Level
Maj
Prt
Min
Obs
Info
Level
Maj
Prt
Min
Obs
Info
Reference
P. 9-29
Reference
P. 9-31
P. 9-31
P. 9-32
P. 9-32
P. 9-33
9
P. 9-34
P. 9-34
Reference
P. 9-35
P. 9-35
9 - 13