9 Troubleshooting
Event code
Event name
65230000 hex
Discrepancy
Error at Safety
Input
65240000 hex
Overload
Detected at Test
Output
65250000 hex
Stuck-at-high
Detected at Test
Output
65270000 hex
Short Circuit
Detected at
Safety Output
65280000 hex
Stuck-at-high
Detected at
Safety Output
 Other Errors
Event code
Event name
80220000 hex
NX Message
Communications
Error
 User Access Log
Event code
Event name
90400000 hex
Event Log
Cleared
90430000 hex
Memory All
Cleared
9 - 16
Meaning
Assumed cause
An error was
• There is a ground fault or dis-
detected in dis-
connection in the input signal
crepancy evalua-
line.
tion of safety
• The connected device is
input terminals.
faulty.
• The setting of the discrepancy
time is not correct.
• Chattering occurred in the
input signal from the external
input device, such as a safety
door.
An overcurrent
• There is a ground fault on the
was detected at
output signal line.
the test output
• The external device is faulty.
terminal.
It was detected
• The positive power supply line
that the test out-
is in contact with the output
put terminal is
signal line.
stuck ON.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software
error or excessive noise.
A ground fault
• There is a ground fault on the
was detected on
output signal line.
the safety output
terminal.
It was detected
• The positive power supply line
that the safety
is in contact with the output
output terminal is
signal line.
stuck ON.
• The output power supply is
outside the specifications.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software
error or excessive noise.
Meaning
Assumed cause
An error was
• The message communications
detected in mes-
load is high.
sage communi-
• The communications cable is
cations for an NX
disconnected or broken.
Unit and the mes-
• Message communications
sage frame was
were cut off as the result of
discarded.
executing a synchronization or
restoration operation on the
Sysmac Studio or as the result
of disconnecting an EtherCAT
slave.
Meaning
Assumed cause
The event log
The event log was cleared by the
was cleared.
user.
The Unit settings
The Clear All Memory operation
were cleared.
was performed.
Level
Maj
Prt
Min
Obs
Level
Maj
Prt
Min
Obs
Level
Maj
Prt
Min
Obs
NX-series Safety Control Unit User's Manual (Z930)
Reference
Info
P. 9-43
P. 9-44
P. 9-44
P. 9-45
P. 9-45
Reference
Info
P. 9-46
Reference
Info
P. 9-47
P. 9-47