Omron NX-SID Series User Manual page 357

Machine automation controller
Hide thumbs Also See for NX-SID Series:
Table of Contents

Advertisement

Event code
Event name
80300000 hex
Safety Process
Data Communi-
cations Timeout
84F1 0000 hex
NX Bus I/O Com-
munications
Stopped
 Safety I/O Errors
Event code
Event name
05210000 hex
Internal Circuit
Error at Safety
Input
05220000 hex
Internal Circuit
Error at Test Out-
put
05230000 hex
Internal Circuit
Error at Safety
Output
65200000 hex
I/O Power Sup-
ply Voltage Error
65210000 hex
Output Power
Interrupt Circuit
Error
65220000 hex
External Test Sig-
nal Failure at
Safety Input
NX-series Safety Control Unit User's Manual (Z930)
Meaning
Assumed cause
A communica-
• A setting is not correct. The
tions timeout
setting of the safety task
occurred in safety
period is too short.
process data
• There is excessive noise.
communications
• The Safety CPU Unit or safety
with the Safety
slave entered a status where it
Control Unit.
could not continue safety pro-
cess data communications.
• An error or status change
occurred in the Communica-
tions Coupler Unit to which the
Unit is connected, preventing
correct process data commu-
nications.
An error occurred
There is a hardware error in the
in I/O communi-
Communications Coupler Unit or
cations between
an NX Unit.
the Communica-
tions Coupler
Unit and an NX
Unit.
Meaning
Assumed cause
A fault was
• The internal circuit for the
detected in the
safety input terminal is faulty.
internal circuit for
• A memory error or signal error
the safety input
occurred due to a transient
terminal.
cause, such as an excessive
noise.
A fault was
• The internal circuit for the test
detected in the
output terminal is faulty.
internal circuit for
• A memory error or signal error
the test output
occurred due to a transient
terminal.
cause, such as an excessive
noise.
A fault was
• The internal circuit for the
detected in the
safety output terminal is faulty.
internal circuit for
• A memory error or signal error
the safety output
occurred due to a transient
terminal.
cause, such as an excessive
noise.
An incorrect I/O
• The input power or output
power supply
power is not supplied cor-
voltage was
rectly.
detected.
An error was
• The wiring is not correct or
detected by the
there is a fault in the hard-
output power
ware.
interruption test.
An error was
• The positive power supply
detected in test
wire is in contact with the input
pulse evaluation
signal line.
of the safety input
• The input signal lines are
terminals.
shorted.
• The external device is faulty.
9 Troubleshooting
Level
Maj
Prt
Min
Obs
Info
Level
Maj
Prt
Min
Obs
Info
Reference
P. 9-39
P. 9-39
Reference
P. 9-40
P. 9-40
P. 9-41
9
P. 9-41
P. 9-42
P. 9-43
9 - 15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents