9 Troubleshooting
Event name
NX Bus Communications Settings and Safety Application
Data Mismatch
Meaning
There is an error in the safety application data that is saved in non-volatile memory.
Source
Depends on where the Sysmac Stu-
dio is connected and the system con-
figuration.
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The NX bus communications settings
that were transferred to the Safety
CPU Unit do not match the safety
application data.
Attached
None
information
Precautions/
None
Remarks
Event name
Non-volatile Memory Access Error
Meaning
Reading/writing non-volatile memory failed.
Source
Depends on where the Sysmac Stu-
dio is connected and the system con-
figuration.
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Non-volatile memory failure
Attached
None
information
Precautions/
None
Remarks
9 - 32
Source details
Minor fault
Recovery
Continues.
Operation
Data type
None
Correction
Transfer the Slave Terminal configu-
ration information and Safety Applica-
tion Data to the Safety CPU Unit
again.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Perform the Clear All Memory opera-
tion or download the settings again.
Replace the CPU Unit if the error
occurs again.
Event code
10520000 hex
NX Unit
Detection timing
When settings
Log category
are transferred
The Safety CPU Unit executes NX bus communications
with the relevant Units but refreshing for the safety pro-
gram stops. (All I/O data will remain at 0.)
Name
None
Prevention
None
Event code
10530000 hex
NX Unit
Detection timing
Clear All Memory
Log category
operation for the
Unit
The Unit continues to operate.
Name
---
Prevention
None
NX-series Safety Control Unit User's Manual (Z930)
When applicable
System
When power is
turned ON to the
NX Unit, when
the operating
mode is changed,
or when Clear All
Memory is exe-
cuted for NX Unit
System