Mitsubishi Electric MELSEC-Q Series User Manual page 7

Melsec-q/l anywireaslink master module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

[Wiring Precautions]
● Individually ground the FG and LG terminals of the programmable controller with a ground resistance
of 100 ohms or less.
Failure to do so may result in electric shock or malfunction.
● Check the rated voltage and terminal layout before wiring to the module, and connect the cables
correctly.
Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire or
failure.
● Tighten the terminal block screws within the specified torque range.
Undertightening can cause short circuit, fire, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, fire, or
malfunction.
● Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
● A protective film is attached to the top of the module to prevent foreign matter, such as wire chips,
from entering the module during wiring.
Do not remove the film during wiring.
Remove it for heat dissipation before system operation.
● Do not apply the 24VDC power before wiring the entire AnyWireASLINK system. If the power is
applied before wiring, normal data transmission is not guaranteed.
● Connect a 24VDC external power supply to the device(s) in an AnyWireASLINK system.
● Do not install the control lines or communication cables together with the main circuit lines or power
cables.
Failure to do so may result in malfunction due to noise.
● Place the cables in a duct or clamp them.
If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or
cables or malfunction due to poor contact.
● When disconnecting the cable from the module, do not pull the cable by the cable part.
For the cable connected to the terminal block, loosen the terminal screw.
Pulling the cable connected to the module may result in malfunction or damage to the module or
cable.
CAUTION
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj51aw12alMelsec-l seriesLj51aw12al

Table of Contents