Mitsubishi Electric MELSEC-Q Series User Manual page 46

Melsec-q/l anywireaslink master module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(2) Transmission cable terminal block
MC 1,5/5-STF-3,81
*1
Use the one manufactured by PHOENIX CONTACT GmbH & Co. KG. (For contact, visit www.phoenixcontact.com.)
Classification
Transmission
cable (DP, DN)
Power supply
cable (24V, 0V)
To tighten the terminal block, a flathead screwdriver having a tipped size of 0.4  2.5mm is required.
Before removing the transmission cable terminal block, check that the terminal block mounting screws on both
ends are completely loosened (removed from the socket).
Pulling the terminal block with excessive force while the terminal block mounting screws on both ends are still
tightened may damage the devices.
Before connecting the terminal block, check that there are no short-circuits due to the disconnected or frayed
wires and tighten the terminal block mounting screws at both ends securely. (Tightening torque: 0.2 to 0.3Nm)
(3) Cable processing
Bare cables can be connected to the transmission cable terminal block; however, for safety reasons, it is
recommended to connect cables using bar solderless terminals.
Use UL-listed solderless terminals and, for processing, use a tool recommended by their manufacturer.
Type
AI 0,75-8 GY
Bar
solderless
AI 1,5-8 BK
*1
terminal
AI-TWIN 2  0,75-8 GY
*1
When connecting two cables to one terminal, connect the two cables together to the TWIN bar solderless terminal.
*2
When TWIN bar solderless terminals are used, the maximum wire diameter is 0.75.
44
Model name
*1
Name
UL-listed general-purpose 2-wire
cable (VCTF, VCT)
UL-listed general-purpose wire
Dedicated flat cable
UL-listed general-purpose 2-wire
cable (VCTF, VCT)
UL-listed general-purpose wire
Dedicated flat cable
Model name
Processing of a 0.752 wire
Processing of a 1.252 wire
Processing of two 0.75 wires
Applicable tightening torque
0.2Nm to 0.3Nm
Wire diameter
1.25
0.75
1.25
Stranded wire
0.75
1.25
0.75
0.75 to 2.0
Stranded wire
Stranded
0.75 to 2.0
wire/single
1.25
Stranded wire
0.75
*2
Application
Temperature
Type
Material
70 or higher
Copper
wire
70 or higher
wire
Contact
PHOENIX CONTACT GmbH & Co. KG
(www.phoenixcontact.com)
rating
90
90