6.2.2

Connection of slave modules

(1) Connection type
Master module
• The maximum transmission distance in the AnyWireASLINK stand-alone system is 200m, which is the total
cable length including the main line and branch line (branch). (It varies depending on the wire diameter of
the transmission cables (DP, DN) or the transmission cable supply current.)
• Tree branch, T-branch, and multidrop connections are usable in the AnyWireASLINK system.
• Up to 128 slave modules can be connected.
The total length of the transmission distance for the AnyWireASLINK system can be calculated from A + B + C.
Note that the total length should not exceed the maximum transmission distance or the total length set for the system to
branch lines.
46
B
Slave
module
Slave
module
Tree-type
A
module
C
Multidrop
Slave
module
T-branch
Terminating
unit
Slave