Functions
6.11 Operation in fieldbus systems
Table 6- 59
Default output process image (master to slave) - Dual slave mode
Bit
Usage
Slave 2
DO0
Motor control bit 0
DO1
Motor control bit 1
DO2
Motor control bit 2
DO3
A / B select
Slave 1
DO0
Serial clock out
DO1
Serial data out
DO2
Quickstop override
DO3
A / B select
(1) The AS-i specification mandates the simultaneous use of 'Motor Left' and 'Motor Right' as fault acknowledge, particu-
larly if there is no spare input available for this function.
(2) If no fault is active then simultaneous operation of 'Motor Left' and 'Motor Right' constitutes a process image error. In
this state both the inverter motor outputs and the motor holding brake outputs are inactive, causing the motor to coast to a
halt and engaging the motor holding brake in exactly the same way as an OFF2 command. This state is maintained until
both 'Motor Left' and 'Motor Right' are deactivated at the same time.
Table 6- 60
Default input process image (slave to master) - Single slave mode
Bit
Usage
DI0
Ready
DI1
Motor active
DI2
Digital input 1
DI3
Digital input 2
174
Description
DO2 DO1 DO0
0
0
0
OFF1
0
0
1
Fixed frequency 1
0
1
0
Fixed frequency 2
0
1
1
Fixed frequency 3
1
0
0
Fixed frequency 4
1
0
1
Fixed frequency 5
1
1
0
Fixed frequency 6
1
1
1
With active trip: Fault ACK (1)
With no Trip: OFF2 (2)
0: 'A' slave active
1: 'B' slave active
Clock signal for CTT2 data transfer from AS-i master
Data signal for CTT2 data transfer from AS-i master
0: Quick stop active
1: Quick stop override: allow Inverter to ignore quick stop
0: 'A' slave active
1: 'B' slave active
Description
0: Inverter is not responsive to AS-i master
1: Inverter is ready to respond to commands from the AS-i master
0: Inverter motor outputs are high impedance
1: Inverter motor outputs are active
0: Input 1 is inactive
1: Input 1 is active
0: Input 2 is inactive
1: Input 2 is active
(default 50 Hz)
(default -50 Hz)
(default 10 Hz)
(default 15 Hz)
(default 20 Hz)
(default 25 Hz)
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB